EasyManua.ls Logo

Calculated Industries ElectriCalc Pro - Voltage Drop Calculations

Calculated Industries ElectriCalc Pro
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User's GUide — 37
KEYSTROKE DISPLAY
1. Set to 3-Phase:
(
)
3 PH
2. Set to 60º C:
(
60º
)
60 3 PH
3. Set to Copper (if necessary):
(
Cu/Al
)
60 Cu 3 PH
4. Enter Volt-Amps:

VA 47,650.
5. Enter Volts:

VOLT 240.
6. Set to 50º C Ambient Temperature:
(
Ambº
)
3Ø 60 Cu Amb AMB° 50. ºC
7. Find Adjusted Wire Size:
AWG 250 CU WIRE SIZE
8. Find Derated Wire Size:
(
D/R Size
)
D/R 500 CU WIRE SIZE
9. Display Wire Ampacity:
D/R 46.5 WIRE A
10. Display Adjustment Factor:
ADJ 41. %
11. Display NEC Table:
NEC 310.15.b.3
12. Reset Ambient Temperature and Clear:

3Ø 60 Cu 0.

Table of Contents

Other manuals for Calculated Industries ElectriCalc Pro

Related product manuals