Passage-open warning light
Signal the door status.
The device is connected to output/terminal 5.
F10 is disabled if the [F18 – Additional light and light signals] function is set to stop/go mode (3) or GGR mode (4).
F10 0 = Warning light on (default) - The light stays on when the door is moving or open.
1 = Warning light flashing - The light flashes every half a second when the door is opening and remains on when the
door is open. The light flashes every second when the door is closing, and remains off when the door is closed.
Soft start
Set a slowdown of a few seconds after each opening and closing command.
F12 OFF
ON (Default)
Closing thrust
At the closing limit-switch, the operator briefly exerts a closing thrust.
F13 OFF (Default)
1 = Minimum thrust
2 = Medium thrust
3 = Maximum thrust
Sensor type
Choose the type of access device.
F14 1 = Keypad (Default)
0 = Transponder
Additional light and light signals
Choose the operating mode of the light connected to outputs 10-E and 10-5.
F18 0 =Flashing beacon (Default)
1 = Cycle light - The lamp stays on during the manoeuvre.
This parameter does not appear if there [Automatic Close] function is deactivated.
2 = Courtesy lamp - The light switches on when a manoeuvre starts and remains on once the manoeuvre has finished,
for the time set under the function [F25 Courtesy time].
3 = Stop/go mode - The light flashes red during opening and closing, and remains on and green when it reaches the
opening limit-switch.
4 = GGR mode - The light flashes green during opening and red during closing, and remains on and green when it
reaches the opening limit-switch.
Automatic closure
Set the time before automatic closure is activated, once the opening travel end point has been reached.
The function does not work if any of the safety devices are triggered when an obstacle is detected, or after a complete stop, or during a power outage.
F19 OFF (Default)
From 1 to 180 seconds
Automatic closing after partial opening
Set the time before automatic closure after a partial opening command.
The function does not work if any of the safety devices are triggered when an obstacle is detected, or after a complete stop, or during a power outage.
Do not deactivate the function [F19 – Automatic close].
F20 OFF (Default)
From 1 to 180 seconds
Pre-flashing time
Adjust the time for which the beacon connected to 10-E is activated before each manoeuvre.
F21 OFF (Default)
1 to 10 seconds
Courtesy time
Define how many seconds the additional light (set up as courtesy light) stays on after an opening or closing manoeuvre.
F25 60 to 180 seconds (Default 60)