Opening speed
Set the opening speed as a percentage.
F28 60% to 100% (Default 80%)
Closing speed
Set the closing speed (percentage of maximum speed).
F29 60% to 100% (Default 80%)
Slowdown speed
Set the slowdown speed as a percentage.
F30 10% to 60% (Default 40%)
Sensitivity for slowed start when closing
Adjust the obstruction detection sensitivity during slowdown when closing, as a percentage.
This function only appears if the [F47 – Slowed start when closing] function is active.
F32 5% to 100% (Default 100%)
5% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity
Calibration speed
Set the travel self-learning speed (percentage of maximum speed).
F33 30% to 60% (Default 50%)
Travel sensitivity
Adjust the obstruction detection sensitivity during boom travel.
F34 10% to 100% (Default 100%)
10% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity
Slowdown sensitivity
Adjust the obstruction detection sensitivity during slowdown in percentage terms.
F35 10% to 100% (Default 100%)
10% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity
Adjusting the partial opening
Set the partial opening percentage of the door.
F36 10% to 80% (Default 40%)
Opening slowdown adjustment
Set the percentage of the total travel to be used for slowdown during opening.
F41 1% to 60% (Default 5%)
Closing slowdown adjustment
Set the percentage of the total travel to be used for slowdown during closing.
F42 1% to 60% (Default 15%)
Adjusting the closing approach
Set the percentage of the total travel to be used for the closing approach.
F44 1% to 10% (Default 10%)
Slowed start when closing
Adjust the slowed start when closing, as a percentage of the total travel of the door.
F47 OFF = Deactivated
1% to 50% (Default 5%)