- TECHNICAL SPECIFICATIONS -
Macroplus and Interfaces
Supply voltage 24 Vac +10% / -15%
Power requirements (controller+main interface) 30 VA max.
Storage temperature -20 ÷ +70°C
Working temperature 0 ÷ 50°C (0 ÷ 65°C interface with NTC probes)
Working humidity 20 ÷ 80 % RH
Working pressure 70KPa (3000 m)
Storage pressure (10000 m)
Weight (controller) 970 g
Macroplus complies with the requirements of IEC 801-2 level 4 (electrostatic noises) and IEC
801-4 level 4 (Burst noises on power supply and I/O cables).
The tests are meant to evaluate the reliability of the instrument and its functioning limits in relation
to a correct installation. All tests have been carried out simulating real situations as indicated by
IEC 801 standards.
Macroplus and its interfaces undergo "test in circuit", the most modern form of computerized test
where all electronic components are controlled. Also a "Burn-in" procedure for 72 hours at 60 °C
is meant to reduce the amount of possible faulty components.
Further automatic and semi-automatic tests ensure the perfect functioning of the controller.
Digital inputs (VOLTAGE-FREE CONTACT)
input current (closed contact) 5 mA
max. resistance 100 Ohms
max. continuous input voltage -5 / +15 Vdc
filter against noises 10ms
Analogue inputs
input signal ± 1 Vdc
resolution 10 bits + sign
max. source resistance 10 Kohms
max. continuous voltage ±50 V
average acquisition time 50 ms/channel
Analogue outputs
max. output variation 0÷10 Vdc ±5%
max. current 10 mA
Resolution D/A 8 bits
rise time 1 s