Modular Standard HP Chiller for Carel driver
Carel code +030221236- Rel. 1.0 dated 7 July 2003
18
Threshold for condensation high temperature
protection during chiller operation
Fs M/S 75,0 0 to 99.9 °C
Integral time of threshold for condensation high
temperature protection during chiller operation
Fs M/S 4,0 0 to 25.5 seconds
Threshold for condensation high temperature
protection during heat pump operation
Ft M/S 75,0 0 to 99.9 °C
Integral time of threshold for condensation high
temperature protection during heat pump operation
Ft M/S 4,0 0 to 25.5 seconds
Threshold for condensation high temperature
protection during defrost. operation
Fu M/S 75,0 0 to 99.9 °C
Integral time of threshold for condensation high
temperature protection during defrost operation
Fu M/S 4,0 0 to 25.5 seconds
Threshold for intake high temperature during chiller
operation
Fv M/S 30,0 0 to 100.0 °C
Threshold for intake high temperature during heat
pump operation
Fw M/S 30,0 0 to 100.0 °C
Threshold for intake high temperature during defrost.
operation
Fx M/S 30,0 0 to 100.0 °C
Type of refrigerant Fy M/S R407c R22 / R134a /
R404a R407c /
R410a / R507c
R290 / R600 /
R600a R717R / 744
CustomValve: minimum steps Fz M/S 0 0 to 8100
CustomValve: maximum steps Fz M/S 1600 0 to 8100
CustomValve: closing steps FA M/S 3600 0 to 8100
CustomValve: return steps FA M/S 0 0 to 8100
CustomValve:
enable extra step at opening
FB M/S N. N/Y
CustomValve: enable extra step at closure FB M/S N. N/Y
CustomValve: current operating FC M/S 250 0 to 1000 mA
CustomValve: current stopped FC M/S 100 0 to 1000 mA
CustomValve: frequency FD M/S 100 32 to 330 Hertz
CustomValve: duty cycle FD M/S 50 0 to 100 %
Minimum value of evaporat. pressure probe FE M/S -0,5 -9.9 to 10.0 Bar
Maximum value of evaporat. pressure probe FE M/S 7,0 3.5 to 200.0 Bar
Delay super heat low alarm FF M/S 0 0 to 3600 seconds
Delay high temperature intake alarm FF M/S 0 0 to 3600 seconds
Delay LOP alarm FG M/S 0 0 to 3600 seconds
Delay MOP alarm FG M/S 0 0 to 3600 seconds
Input new constructor-driver password FH M/S 1234 0 to 9999
M/S

Table of Contents

Other manuals for Carel pCO1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel pCO1 and is the answer not in the manual?

Carel pCO1 Specifications

General IconGeneral
BrandCarel
ModelpCO1
CategoryChiller
LanguageEnglish

Related product manuals