13 Inspection & Maintenance functions
Last three faults are stored in a stack and whenever there is a new fault the previous faults are
pushed down the stack. So the fault stored in 2.xxx will be transferred to 3.xxx, and the one in
1.xxx to 2.xxx. The recent fault will be stored in the empty register 1.xxx.
Use up and down keys to scroll between the fault registers.
Pressing reset key when parameter 13-02 is displayed then all three fault registers will be
cleared and the display for each register will change to 1. ---, 2. ---, 3. ---.
E.g. fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc.
13-00 Drive Horsepower Code
Range -----
13-01 Software Version
Range -----
13-02 Fault Log Display (Latest 3 faults)
Range -----
Inverter Model: 13-00 show Inverter Model: 13-00 show
RVLFA120020FA 120020FA RVLFA110040A 110040A
RVLFA120040FA 120040FA RVLFA110075A 110075A
RVLFA120075FA 120075FA RVLFB340075FA 340075FA
RVLFB120150FA 120150FA RVLFB340150FA 340150FA
RVLFB120220FA 120220FA RVLFB340220FA 340220FA
RVLFA320040A 320040A RVLFC340370FA 340370FA
RVLFA320075A 320075A RVLFC340550FA 340550FA
RVLFB320150A 320150A RVLFD340750FA 340750FA
RVLFB320220A 320220A RVLFD3401100FA 3401100FA
13-03 Accumulated Inverter Operation Time 1
Range [0~23] Hours
13-04 Accumulated Inverter Operation Time 2
Range [0~65535] Days
13-05 Accumulated Inverter Operation Time Mode
Range
[0] Power on time
[1] Operation time
13-06 Parameter lock
Range
[0] Enable all functions
[1] Preset speeds 05- 01~05- 08 cannot be changed
[2] All Functions cannot be changed except for preset speeds set in 05-01~05- 08
[3] Disable all function except 13-06
When the operation time recorded in accumulator 1 (Parameter 13-03) reaches 24 hours,
the recorded value in accumulator 2 (parameter 13-04) changes to 1 day and the value in
accumulator 1 is reset to 0000.
When the 13-07=00000 (not set a password), you can adjust the parameters 05-01~05-08
from 13-06.