EasyManuals Logo

Carlyle 06D Service Manual

Carlyle 06D
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
143
COMP/ALARM
The compressor contactor output is a relay output. The relay
operating voltage is 24 to 240 VAC with a maximum con-
tinuous current of 2.5 amps (600 VA). The compressor
COMP contactor will open when any of the following con-
ditions exist:
Loss of 24 VAC supply power
Discharge temperature sensor failure, discharge tem-
perature >295 F
The input demand voltage is > 8.0 VDC.
The Comp/Alarm contactor should be wired into the
compressor’s control power circuit if the Carlyle dis-
charge temperature sensor is being used to control com-
pressor discharge temperature. This will ensure the
compressor will shut down if discharge temperature
exceeds 295 F or sensor fails. The triac output for Coil 1,
Coil 2, and the LIV (Liquid Injection Valve) will open, dis-
abling the unloader valves and liquid injection valve if the
Comp/Alarm contactor is opened.
CYLINDER HEAD FAN LEAD WIRES
The smart controller has two 6-in. lead wires for wiring to
the compressor’s cylinder head fan. The smart controller
will energize/de-energize the internal cylinder head fan
relay as required to maintain discharge temperatures below
220 F. The lead wires are rated for 230/460 VAC with a
maximum continuous rating of 2.5 amps.
AC IN
Line voltage input to provide power to the unloader solenoid
coils and the liquid injection solenoid coil. Rated for 115/
208-230 VAC with a maximum continuous rating of 30 VA.

Table of Contents

Other manuals for Carlyle 06D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carlyle 06D and is the answer not in the manual?

Carlyle 06D Specifications

General IconGeneral
BrandCarlyle
Model06D
CategoryAir Compressor
LanguageEnglish

Related product manuals