Carrier 19DV Series - Page 82

Carrier 19DV Series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
Cond Pre Override Dv 72
379.2
379.2
Cond Pre Cutout DV 72
406.8
406.8
Condenser freeze point
1.1
1.1
Comp discharge Alert
93.3
93.3
Comp Motor Temp Override
93.3
93.3
Comp Bearing Temp Alert
79.4
79.4
Comp Bearing Temp trip
85
85
Comp Bearing Alert R6/7
98.9
98.9
Comp Bearing Trip R6/7
104.4
104.4
Comp Bearing Alert DV
40
40
Comp bearing Trip DV
50
50
Minimum Brine LWT
1.1
1.1
Heating LWT Protect Set
6
6
Liquid Bypass Temp Band
1.7
1.7
Evap Flow Delta P Cutout
35
Jobsite specific
Cond Flow Delta P Cutout
35
Jobsite specific
Cond Hi Flow DP Limit
344.7
Jobsite specific
Cond Hi Flow Alarm
Disable
Disable
TABLE
General Configuration
Access Menu
Configuration Menu / General Configuration
Setting
Default value
(SI units)
Settings value (SI)
User password
1111
1111
Stop to Start Delay
2
2
Start to Start Delay
15
15
Demand limit Type (Base demand=0, 4-20mA=1)
0
0
Pulldown rampe type (Temp=0, Load=1)
1
1
Demand limit source (Amps=0, kW=1)
0
0
TABLE
CFGEVFD - General VFD Config
Access Menu
Configuration Menu / General VFD Config
Setting
Default value (SI units)
Settings value (SI)
Comments
VFD gain
0.75
0.75
VFD Max Speed Per
100%
100%
VFD Min Speed Per
70%
55%
VFD Start Speed Per
100%
100%
VFD Current limit
250 A
872
Max current output for UM VFD
VFD Load Current 20mA
200 A
200 A
Comp Frequency 100%
50 Hz
50 Hz
VFD load current input
Enable
Enable
TABLE
19DV Configure
Access Menu
Configuration Menu / 19DV Config
Setting
Default value (SI units)
Settings value (SI)
Pressure sensor option (Tianmu=0,
Texas=1, Sensata=2)
0
0
Motor pole pair
1
1
IGV2 Travel limit
100%
96.0%
IGV2 Minimum Deg
2
2
IGV2 Full Load open Deg
88
90
IGV2 Actuator Max Deg
94
94
IGV2 Deg @IGV1 20 Deg
28.1
28.1
IGV2 Deg @IGV1 30 Deg
37.2
37.2
IGV2 Deg @IGV1 50 Deg
71.6
71.6
Comp Based Speed Hz
80.5
80.5
Purge Regen Lasting time
120
120
Daily PG Pumpout Limit
50 min
50 min
DSH_Req param VFD F
0.5
0.5
DSH_Req param VFD 2nd
-0.0059
-0.0059