83
DSH_Req param VFD 1st
0.9427
0.9427
DSH_Req param VFD Const
-34.5
-34.5
DSH_Req param IGV F
0.2
0.2
DSH_Req param IGV 2nd
0.0046
0.0046
DSH_Req param IGV 1st
-0.562
-0.562
DSH_Req param IGV Const
21
21
DSH_Req param Lift F
0.3
0.3
DSH_Req param Lift 2nd
0.0006
0.0006
DSH_Req param Lift 1st
-0.1104
-0.1104
DSH_Req param Lift Const
5.5
5.5
Liquid Bypass Temp Diff
11.1
11.1
Liquid Bypass Cond Appro
2.8
2.8
Bearing Sub Cooling
-5
-5
Purge Discharge Temp
-15.6
-15.6
Purge Drainage Temp
-11.1
-11.1
CLT Factory Option
disable
enable
Refrig Lube Option 7
disable
disable
TABLE
CFGUMVFD - UM VFD Configuration
Access Menu
Configuration Menu / UM VFD Configuration
Setting
Default value (SI units)
Settings value (SI)
Comments
Compressor Speed 100%
50 Hz
98 Hz
Nameplate
Rated line voltage
460 V
400 V
Nameplate
Motor Nameplate Current
200 A
Nameplate
Motor Rated Load Current
200 A
Nameplate
Motor Nameplate Voltage
460 V
Nameplate
Motor Nameplate RPM
3000 rpm
Nameplate
Motor Nameplate KW
1500 kW
Nameplate
Skip Frequency 1
102 Hz
102 Hz
UM Rockwell LF2
Skip Frequency 2
102 Hz
102 Hz
UM Rockwell LF2
Skip Frequency 3
102 Hz
102 Hz
UM Rockwell LF2
Skip Frequency Band
0 Hz
0 Hz
Increase Ramp Time
30 sec
30 sec
Decrease Ramp Time
30 sec
30 sec
Line Voltage % Imbalance
0.1
10%
Line Volt Imbalance Time
10 sec
10 sec
Line Current % Imbalance
0.4
40%
Line Current Imbal Time
10 sec
10 sec
Motor Current % Imbalance
0.4
40%
Motor Current Imbal Time
10 sec
10 sec
Single Cycle Dropout
Dsable
Dsable
PWM Frequency (0=2 k Hz, 1=4 k Hz)
0
0
Restore Defaults
No
No
LEN Comm Timeout
10 sec
10 sec
Modbus Comm Timeout
2 sec
2 sec
Gateway Modbus Baud Rate
4800 = 1, 9600 = 2, 19200 = 3,
38400=4
2
2
Number of GDCBs
0
0
GDCB Startup Delay
50%
50%
TABLE
CONF_OPT - Option configuration
Access Menu
Configuration Menu / Option Configuration
Setting
Default value (SI units)
Settings value (SI)
Auto Restart Option
Dsable
job site specific
Common Sensor Option
Dsable
job site specific
EC Valve Option
No=0, Cont.=1, ON/OFF=2, mA=3
0
2 if selected
EC valve selection
Disable =0, Surge=1, Low Load=2, Comb=3
0
job site specific
ECV Open IGV1 Position
5%
5% (adjust as required)
ECV Close IGV1 Position
10%
10% (adjust as required)
ECV Off DT for Low Load
2,2 °C
2,2 °C (adjust as required)