Carrier 38APS025 - C.TYP=8 (Dual Tstat) Wiring

Carrier 38APS025
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
106
REMOTE ON/OFF
DEMAND
LIMIT
SIGNAL
4-20 mA
SIGNAL
GENERATOR
T2-Y2
T2-Y1
38AP LVT
TERMINAL STRIP
+
FS1
25
24
18
17
16
15
14
13
12
8
7
6
5
4
3
2
1
ALM
R
FS2
T1-Y2
T1-Y1
T1-
Y1
T1-
Y2
T2-
Y1
T2-
Y2
R
Y1
Y2
W1
W2
G
C
X
AHU2 (CIRCUIT B)
THERMOSTAT
(REQUIRED)
R
Y1
Y2
W1
W2
G
C
X
AHU1 (CIRCUIT A)
THERMOSTAT
(REQUIRED)
FIELD-SUPPLIED
TRANSFORMER
(REQUIRED)
24 VAC
SECONDARY
(REQUIRED)
(REQUIRED)
(REQUIRED)
(REQUIRED)
CXB-J6
(38APD070-130 ONLY)
FIELD-SUPPLIED
TRANSFORMER
(REQUIRED)
RED
7
6
5
PNK
ORN
LLSV-A2
LLSV-B2
24 VAC
SECONDARY
LLSV-B
LLSV-A
Fig. 140 — C.TYP=8 (Dual Tstat) Wiring
LEGEND
NOTES:
1. AHU1 is connected to 38APD — Circuit A.
AHU2 is connected to 38APD — Circuit B.
2. Field wiring must be in accordance with local codes.
3. LVT-1 and 2 are for the alarm relay. The maximum load allowed for the alarm relay
is 5 VA sealed, 10 VA at 24 VAC. Field power supply is not required.
4. LVT-24, 25, and 2 are for control of field-supplied liquid line solenoid valve (LLSV)
15 VA sealed, 30 VA inrush at 24 VAC. Field power supply is not required.
5. For 38APD070-130 units, an additional LLSV, 15 VA sealed, 30 VA inrush at 24
VAC can be connected to CXB. A field-supplied control transformer is required, not
to exceed 75 VA.
6. All discrete inputs are 24 VAC.
7. Installation of fan status switches (FS1, FS2) is recommended. If not used, a
jumper must be installed.
8. Energy management module (EMM) is required.
9. This control scheme does not support digital compressor operation.
10. The contacts for Remote On-Off, Fan Status Switch and Demand Limit must be
rated for dry circuit applications capable of handling a 24 VAC load up to 50 mA.
11. Single or 2-Step Demand Limit is not available with this control type.
AHU Air-Handling Unit
ALM R Alarm Relay
CXB Compressor Expansion Board
FS1 Fan Status Switch, AHU1
FS2 Fan Status Switch, AHU2
LLSV-A Liquid Line Solenoid, Circuit A, First Stage
LLSV-A2 Liquid Line Solenoid, Circuit A, Second Stage (38APD070-130 only)
LLSV-B Liquid Line Solenoid, Circuit B, First Stage
LLSV-B2 Liquid Line Solenoid, Circuit B, Second Stage (38APD070-130 only)
LVT Low Voltage Terminal
T1 AHU1 Thermostat
T2 AHU2 Thermostat
——— Factory Wiring
--------- Field Wiring