119
Table 46 — 38APD,APS040-050 Fan Staging
*Items in either Service Test
OUTS or Outputs
GEN.O.
†Motormaster controlled motor.
Table 47 — 38APD060, 38APS065 Fan Staging
*Items in either Service Test
OUTS or Outputs
GEN.O.
†Motormaster controlled motor, if equipped.
UNIT OPERATING CIRCUIT FAN STAGE OUTPUT POINT NAME* CONTACTOR FANS ENERGIZED
38APD040,050
38APS040,050
Without Motormaster
®
Controller
A (38APS)
A or B (38APD)
1FAN1FC1OFM3
2 FAN2 FC2 OFM1, OFM2
3
FAN1
FAN2
FC1
FC2
OFM3
OFM1, OFM2
38APD040,050
38APS040,050
With Motormaster Controller
A (38APS)
A or B (38APD)
1FAN1FC1OFM3†
2
FAN1
FAN2
FC1
FC2
OFM3†
OFM1, OFM2
UNIT OPERATING CIRCUIT FAN STAGE OUTPUT POINT NAME* CONTACTOR FANS ENERGIZED
38APD060
Without Motormaster Controller
A or B
1FAN1FC1OFM3
2
FAN1
FAN2
FC1
FC2
OFM3
OFM1, OFM2
3
FAN1
FAN3
FC1
FC3
OFM3, OFM4
4
FAN1
FAN2
FAN3
FC1
FC2
FC3
OFM3
OFM1, OFM2
OFM4
38APD060
With Motormaster Controller
A or B
1FAN1FC1OFM3†
2
FAN1
FAN3
FC1
FC3
OFM3†, OFM4
3
FAN1
FAN2
FC1
FC2
OFM3†
OFM1, OFM2
4
FAN1
FAN2
FAN3
FC1
FC2
FC3
OFM3†
OFM1, OFM2
OFM4
38APS065
With or Without Motormaster
Controller
B
1FAN1FC1OFM3†
2
FAN1
FAN3
FC1
FC3
OFM3†, OFM4
3 FAN2 FC2 OFM1, OFM2
4
FAN1
FAN2
FC1
FC2
OFM3†
OFM1, OFM2
5
FAN1
FAN2
FAN3
FC1
FC2
FC3
OFM3†
OFM1, OFM2
OFM4
CONTROL BOX
OFM1
OFM2
OFM3