EasyManua.ls Logo

Carrier 38APS025 - 38 APD,APS040-050 Fan Staging; 38 APD060, 38 APS065 Fan Staging

Carrier 38APS025
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
Table 46 — 38APD,APS040-050 Fan Staging
*Items in either Service Test
o
OUTS or Outputs
o
GEN.O.
†Motormaster controlled motor.
Table 47 — 38APD060, 38APS065 Fan Staging
*Items in either Service Test
o
OUTS or Outputs
o
GEN.O.
†Motormaster controlled motor, if equipped.
UNIT OPERATING CIRCUIT FAN STAGE OUTPUT POINT NAME* CONTACTOR FANS ENERGIZED
38APD040,050
38APS040,050
Without Motormaster
®
Controller
A (38APS)
A or B (38APD)
1FAN1FC1OFM3
2 FAN2 FC2 OFM1, OFM2
3
FAN1
FAN2
FC1
FC2
OFM3
OFM1, OFM2
38APD040,050
38APS040,050
With Motormaster Controller
A (38APS)
A or B (38APD)
1FAN1FC1OFM3
2
FAN1
FAN2
FC1
FC2
OFM3†
OFM1, OFM2
CONTROL BOX
OFM1
OFM2
OFM3
UNIT OPERATING CIRCUIT FAN STAGE OUTPUT POINT NAME* CONTACTOR FANS ENERGIZED
38APD060
Without Motormaster Controller
A or B
1FAN1FC1OFM3
2
FAN1
FAN2
FC1
FC2
OFM3
OFM1, OFM2
3
FAN1
FAN3
FC1
FC3
OFM3, OFM4
4
FAN1
FAN2
FAN3
FC1
FC2
FC3
OFM3
OFM1, OFM2
OFM4
38APD060
With Motormaster Controller
A or B
1FAN1FC1OFM3
2
FAN1
FAN3
FC1
FC3
OFM3†, OFM4
3
FAN1
FAN2
FC1
FC2
OFM3†
OFM1, OFM2
4
FAN1
FAN2
FAN3
FC1
FC2
FC3
OFM3†
OFM1, OFM2
OFM4
38APS065
With or Without Motormaster
Controller
B
1FAN1FC1OFM3
2
FAN1
FAN3
FC1
FC3
OFM3†, OFM4
3 FAN2 FC2 OFM1, OFM2
4
FAN1
FAN2
FC1
FC2
OFM3†
OFM1, OFM2
5
FAN1
FAN2
FAN3
FC1
FC2
FC3
OFM3†
OFM1, OFM2
OFM4
CONTROL BOX
OFM1
OFM2
OFM3
OFM4

Table of Contents