EasyManua.ls Logo

Carrier 38APS025 - A175 - Loss of Communication with AUX Board; T176 - 4 to 20 Ma Reset Input Failure; T177 - 4 to 20 Ma Demand Limit Input Failure; T303 - Coil - Scheduled Maintenance Due

Carrier 38APS025
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
175
A175 — Loss of Communication with AUX board
Criteria for Trip: A communication problem with the AUX
Board has been detected by the Main Base Board. The AUX
Board is required for digital compressor operation and low
ambient head pressure control (Motormaster
®
) operation.
Action to be taken: Functions associated with the AUX Board,
digital compressor and Motormaster controller operation are
stopped.
Reset Method: Automatic once the condition is resolved.
Possible Causes: If this condition is encountered, check the
following items:
Check the configurations. If Compressor A1 Digital
Configuration
o
UNIT
o
A1.TY=YES and no AUX
Board is installed, this alarm will be generated. Simi-
larly, if Motormaster Select Configuration
o
M.MST
o
MMR.S=YES and no AUX Board is installed, this alarm
will be generated.
Check the address of the AUX Board.
Check the LEN wiring to the AUX Board.
Check the power supply to the AUX Board.
T176 — 4 to 20 mA Reset Input Failure
Criteria for Trip: This alert indicates a problem has been
detected with reset 4 to 20 mA input. The input value is either
less than 2 mA or greater than 22 mA.
Action to be taken: The cooling reset function will be disabled
when this occurs.
Reset Method: Manual
Possible Causes: If this condition is encountered, check the
following items:
Confirm the input signal the control is reading. Check
the value of 4-20 Reset Signal (Inputs Mode
o
4-20
o
RSET). Compare this to expected signal strength.
Confirm signal polarity, LVT-8 (–) and LVT-9 (+)
Confirm Energy Management Module configuration,
EMM Module Installed, Configuration
o
OPT1
o
EMM=YES.
T177 — 4 to 20 mA Demand Limit Input Failure
Criteria for Trip: This alert indicates that a problem has been
detected with demand limit 4 to 20 mA input. The input value
is either less than 2 mA or greater than 22 mA.
Action to be taken: The cooling demand limit function will be
disabled when this occurs.
Reset Method: Manual.
Possible Causes: If this condition is encountered, check the
following items:
Confirm the input signal the control is reading. Check
the value of 4-20 Demand Signal (Inputs Mode
o
4-20
o
DMND). Compare this to expected signal strength.
Confirm signal polarity, LVT-8 (–) and LVT-7 (+)
Confirm Energy Management Module configuration,
EMM Module Installed, Configuration
o
OPT1
o
EMM=YES.
A200 — Indoor Fan Status Failure - Fan Not Running
Criteria for Trip: This alarm is generated when the following
conditions are true:
1. 38AP unit is Enabled (Inputs
o
GEN.I
o
STST=STRT).
2. Airflow switch is open (Inputs
o
GEN.I
o
ID.F.A=
OFF).
Action To Be Taken: Unit is not allowed to start, or is shut
down.
Reset Method: Automatic once the condition is resolved.
Possible Causes: If this condition is encountered, check the
following items:
Confirm that airflow is present in the air handler if an air-
flow switch is used.
Check airflow switch circuit wiring.
If no airflow switch is used, confirm the jumper is in
place between LVT-16 and LVT-18.
T201 — Circuit A Indoor Fan Status Failure - Fan Not
Running
T202 — Circuit B Indoor Fan Status Failure - Fan Not
Running
Criteria for Trip: This alarm is generated when the following
conditions are true:
1. 38AP unit is Enabled (Inputs
o
GEN.I
o
STST=STRT).
2. Control Type is Dual Thermostat (Configuration
o
OPT2
o
C.TYP=8).
3. Airflow switch 1 is open (Inputs
o
GEN.I
o
ID.F.A=
OFF) (T201) or airflow switch 2 is open (Inputs
o
GEN.I
o
ID.F.B=OFF) (T202).
Action To Be Taken: For T201, circuit A is not allowed to start,
or is shut down. For T202, circuit B is not allowed to start, or
is shut down.
Reset Method: Automatic once the condition is resolved.
Possible Causes: If this condition is encountered, check the
following items:
Confirm that airflow is present in the air handler if an air-
flow switch is used.
Check airflow switch circuit wiring.
If no airflow switch 1 is used, confirm the jumper is in
place between LVT-16 and LVT-18 for T201.
If no airflow switch 2 is used, confirm the jumper is in
place between LVT-17 and LVT-18 for T202.
T303 — Coil - Scheduled Maintenance Due
Criteria for Trip: This alarm is generated when the Coil Ser-
vice Countdown (Run Status
o
PM
o
COIL
o
C.L.DN) has
expired.
Action To Be Taken: None, service alert only.
Reset Method: Manual. Perform coil maintenance. Before the
alert can be cleared, Coil Cleaning Maint Done (Run Status
o
PM
o
COIL
o
C.L.MN) must be toggled from NO to YES.
Reset the alert.
Possible Causes: If this condition is encountered, check Coil
Service Countdown.
T500 — Current Sensor Board A1 Failure
T501 — Current Sensor Board A2 Failure
T502 — Current Sensor Board A3 Failure
T503 — Current Sensor Board B1 Failure
T504 — Current Sensor Board B2 Failure
T505 — Current Sensor Board B3 Failure
Criteria for Trip: This alarm is generated when the Current
Sensing Board (CSB) output read by the Main Base Board
(MBB) or Compressor Expansion Module (CXB) is at a con-
stant high value.
Action To Be Taken: Affected compressor is shut down.
Reset Method: Automatic, when signal returns to normal.
Possible Causes: If this condition is encountered, check the
following items:
Check the CSB to be sure that it is wired properly.
On 208 volt systems, be sure that the control transformer
is wired for 208 volts. It has been noted with some sys-
tems that operate on 208 volts, when the wire is located
on the 230 volt tap, nuisance T500-T505 alarms have
been generated.
Consider replacing the CSB.
o
515

Table of Contents

Related product manuals