226
APPENDIX E — CONTROL METHODS WITH INPUTS FOR CONTROL MODE COMPARISON (cont)
CTRL DESCRIPTION
ENABLE-
OFF-
REMOTE
SWITCH
OCCUPANCY
SCHEDULE
CHIL_S_S
VALUE
EMSTOP
VALUE
INDOOR
FAN
STATUS
SWITCH
SPT
SATISFIED
(C.TYP=3
OR 5)
ALARM STAT
3 CCN
Enable
N/A Start
Enable Closed No No 6 (ON CCN)
Enable Closed Yes No 9 (SPT SATISFIED)
Enable Open Yes/No No 8 (IDFS NOT ON)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
N/A Stop
Enable Closed/Open Yes/No No 2 (OFF CCN)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Off N/A Start/Stop
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Remote-
Open
N/A Start/Stop
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Remote-
Closed
N/A Start
Enable Closed No No 6 (ON CCN)
Enable Closed Yes No 9 (SPT SATISFIED)
Enable Open Yes/No No 8 (IDFS NOT ON)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
N/A Stop
Enable Closed/Open Yes/No No 2 (OFF CCN)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)