APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List
LEGEND
POINT DESCRIPTION CCN POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
4-20 Cooling Demand COOL_MA R mA 0-20 AV:6 cool_ma_1
4-20 mA Demand Signal LMT_MA R mA 0-20 AV:36 lmt_ma_1
4-20 mA Reset Signal RST_MA R mA 0-20 AV:33 rst_ma_1
Active Demand Limit DEM_LIM R/W % 100 0-100 AV:2 dem_lim_1
Active Setpoint SP R °F -20-70 AV:4 sp_1
Alarm State
MSV Point for i-Vu /
BACnet based on
CCN point ALM
R
0 = Normal
1 = Alert
2 = Alarm
MSV:1 alm_msv_1
CCN Chiller CHIL_S_S R/W Start
0 = Stop
1 = Start
BV:4 chil_s_s_1
CCN Loadshed Signal DL_STAT R 0-2 AV:37 dl_stat_1
Circuit A Run Hours HR_CIRA R hr 0-9999 AV:59 hr_cira_1
Circuit A Starts CY_CIRA R 0-9999 AV:67 cy_cira_1
Circuit B Run Hours HR_CIRB R hr 0-9999 AV:63 hr_cirb_1
Circuit B Starts CY_CIRB R 0-9999 AV:71 cy_cirb_1
Coil Cleaning Maint.Done CL_MAINT R/W No
0 = No
1 = Yes
BV:54 cl_maint_1
Coil Cleaning Srvc Inter SI_COIL R/W hr 8760 0-9999 AV:50 si_coil_1
Coil Service Countdown CL_CDOWN R hr 0-9999 AV:49 cl_cdown_1
Comp A1 Load Percent DIGITALP R % 0-100 AV:34 digitalp_1
Compr Return Gas Temp RGTA R °F 0-125 AV:20 rgta_1
Compr Return Gas Temp RGTB R °F 0-125 AV:28 rgtb_1
Compressor A1 Feedback K_A1_FBK R ON_OFF BV:16 k_a1_fbk_1
Compressor A1 Relay K_A1_RLY R ON_OFF BV:13 k_a1_rly_1
Compressor A1 Run Hours HR_A1 R hr 0-9999 AV:60 hr_a1_1
Compressor A1 Starts CY_A1 R 0-9999 AV:68 cy_a1_1
Compressor A2 Feedback K_A2_FBK R ON_OFF BV:17 k_a2_fbk_1
Compressor A2 Relay K_A2_RLY R ON_OFF BV:14 k_a2_rly_1
Compressor A2 Run Hours HR_A2 R hr 0-9999 AV:61 hr_a2_1
Compressor A2 Starts CY_A2 R 0-9999 AV:69 cy_a2_1
Compressor A3 Feedback K_A3_FBK R ON_OFF BV:18 k_a3_fbk_1
Compressor A3 Relay K_A3_RLY R ON_OFF BV:15 k_a3_rly_1
Compressor A3 Run Hours HR_A3 R hr 0-9999 AV:62 hr_a3_1
Compressor A3 Starts CY_A3 R 0-9999 AV:70 cy_a3_1
Compressor B1 Feedback K_B1_FBK R ON_OFF BV:22 k_b1_fbk_1
Compressor B1 Relay K_B1_RLY R ON_OFF BV:19 k_b1_rly_1
Compressor B1 Run Hours HR_B1 R hr 0-9999 AV:64 hr_b1_1
Compressor B1 Starts CY_B1 R 0-9999 AV:72 cy_b1_1
Compressor B2 Feedback K_B2_FBK R ON_OFF BV:23 k_b2_fbk_1
Compressor B2 Relay K_B2_RLY R ON_OFF BV:20 k_b2_rly_1
Compressor B2 Run Hours HR_B2 R hr 0-9999 AV:65 hr_b2_1
Compressor B2 Starts CY_B2 R 0-9999 AV:73 cy_b2_1
Compressor B3 Feedback K_B3_FBK R ON_OFF BV:24 k_b3_fbk_1
Compressor B3 Relay K_B3_RLY R ON_OFF BV:21 k_b3_rly_1
Compressor B3 Run Hours HR_B3 R hr 0-9999 AV:66 hr_b3_1
Compressor B3 Starts CY_B3 R 0-9999 AV:74 cy_b3_1
Control Method
MSV Point for i-Vu /
BACnet based on
CCN point
CONTROL
R0
0 = Switch
1 = Occupancy
2 = CCN
MSV:5 control_msv_1
Control Mode STAT R
0 = Test
1 = Local Off
2 = CCN Off
3 = Clock Off
4 = Emergency
Stop
5 = Local On
6 = CCN On
7 = Clock On
8 = IDF Off
9 = SPT SATS
AV:8 stat
Control Point CTRL_PNT R/W °F -20-70 AV:5 ctrl_pnt_1
R—Read
W—Write