APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Cooling Demand Level R 0-3 AV:9006 cool_demand_level_1
Cooling Ramp Loading CRAMP R/W °F 1.0 0.2-2.0 AV:56 cramp_1
Cooling Reset Type
MSV Point for i-Vu
/ BACnet based
on CCN point
CRST_TYP
R0
0 = No Reset
1 = 4-20 mA Input
2 = Outdoor Air Temp
3 = Return Temperature
4 = Space Temperature
MSV:7 crst_typ1_msv_1
Cooling Setpoint 1 CSP1 R/W °F 60.0 -20-70 AV:53 csp1_1
Cooling Setpoint 2 CSP2 R/W °F 55.0 -20-70 AV:54 csp2_1
Demand Level 1 R/W 0-100 AV:80 dmv_lvl_1_perct
Demand Level 2 R/W 0-100 AV:81 dmv_lvl_2_perct
Demand Level 3 R/W 0-100 AV:82 dmv_lvl_3_perct
Demand Limit Select
MSV Point for i-Vu
/ BACnet based
on CCN point
DMD_CTRL
R0
0 = None
1 = Ext. Sw. Input
2 = 4-20 mA Input
3 = CCN Loadshed
MSV:8 dmd_ctrl_msv_1
Demand Limit Switch 1 DMD_SW1 R ON_OFF BV:25 dmd_sw1_1
Demand Limit Switch 2 DMD_SW2 R ON_OFF BV:26 dmd_sw2_1
Demand/Sound Limited MODE_15 R ON_OFF BV:41 mode_15_1
Discharge Gas Temp DIGCMPDT R °F -40-245 AV:7 digcmpdt_1
Discharge Pressure DP_A R psig 0-999 AV:13 dp_a_1
Discharge Pressure DP_B R psig 0-999 AV:23 dp_b_1
Element Communications
Alarm
R
0 = Comm Normal
1 = Comm Alarm
BV:58
(BALM)
comm_lost_alm
Element Comm Status R
0 = No Comm
1 = Normal
BV:2999 element_stat_1
Emergency Stop EMSTOP R/W 0
0 = Enable
1 = Emstop
BV:6 emstop_1
Fan 1 Relay FAN_1 R ON_OFF BV:60 fan_1_1
Fan 2 Relay FAN_2 R ON_OFF BV:61 fan_2_1
Fan 3 Relay FAN_3 R ON_OFF BV:62 fan_3_1
Fan 4 Relay FAN_4 R ON_OFF BV:63 fan_4_1
Fan 5 Relay FAN_5 R ON_OFF BV:64 fan_5_1
Fan Delta Active Time FANDLTTM R/W sec 0-999 AV:10 fandlttm_1
Fan Stage Circuit A FANSTGEA R sec 0-999 AV:35 fanstgea_1
Fan Stage Circuit B FANSTGEB R sec 0-999 AV:15 fanstgeb_1
Head Set Point OFF HSP_OFF R/W °F 72 0-150 AV:16 hsp_off_1
Head Set Point ON HSP_ON R/W °F 110 0-150 AV:18 hsp_on_1
Hi Cool On Set Point DMDHCON R/W °F 3 0.5-20 AV:25 dmdhcon_1
High SCT Circuit A MODE_21 R ON_OFF BV:47 mode_21_1
High SCT Circuit B MODE_22 R ON_OFF BV:48 mode_22_1
High Temperature Cooling MODE_18 R ON_OFF BV:44 mode_18_1
Indoor Fan Status-CIRA IDFA_FS R ON_OFF BV:2 idfa_fs_1
Indoor Fan Status-CIRB IDFB_FS R ON_OFF BV:3 idfb_fs_1
Lead/Lag Circuit Select LEAD_TYP R/W 1
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
AV:43 lead_typ_1
Liquid Line Solenoid A LLSV_A R ON_OFF BV:8 llsv_a_1
Liquid Line Solenoid B LLSV_B R ON_OFF BV:9 llsv_b_1
Lo Cool Off Set Point DMDLCOFF R/W °F 0.5 0.5-2 AV:30 dmdlcoff_1
Lo Cool On Set Point DMDLCON R/W °F 1 -1-2 AV:31 dmdlcon_1
Loading Sequence Select SEQ_TYPE R/W 1 1-2 AV:77 seq_type_1
Low Sound Mode MODE_25 R ON_OFF BV:51 mode_25_1
Low Temperature Cooling MODE_17 R ON_OFF BV:43 mode_17_1