178
APPENDIX A — DISPLAY TABLES (cont)
Run Status Mode and Sub-Mode Directory (cont)
Service Test Mode and Sub-Mode Directory
SUB-MODE ITEM
SUB-
ITEM
SUB-
SUB-ITEM
DISPLAY ITEM DESCRIPTION COMMENT
STRT
COMPRESSOR STARTS
ST.A1 XXXX Compressor A1 Starts
ST.A2 XXXX Compressor A2 Starts
ST.A3 XXXX Compressor A3 Starts
ST.B1 XXXX Compressor B1 Starts
ST.B2 XXXX Compressor B2 Starts
ST.B3 XXXX Compressor B3 Starts
PM
PREVENTIVE MAINTENANCE
COIL
COIL MAINTENANCE
SI.CL XXXX HRS Coil Cleaning Srvc Int
Range: 0 to 65,500 hrs
Default: 8760 hrs
C.L.DN XXXX HRS Coil Service Countdown
C.L.MN YES/NO Coil Cleaning Maint.Done User Input
CL.DT
COIL MAINTENANCE DATES
C.L.M0 MM/DD/YY HH:MM
C.L.M1 MM/DD/YY HH:MM
C.L.M2 MM/DD/YY HH:MM
C.L.M3 MM/DD/YY HH:MM
C.L.M4 MM/DD/YY HH:MM
VERS
SOFTWARE VERSION NUMBERS
MBB CESR131466-XXXXX
AUX CESR131333-XXXXX
CXB CESR131173-XXXXX
EMM CESR131174-XXXXX
MARQ CESR131171-XXXXX
NAVI CESR130227-XXXXX
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
TEST ON/OFF Service Test Mode
To enable Service Test mode, move
Enable/Off/Remote contact switch to
OFF. Change TEST to ON and move
switch to ENABLE
OUTS
OUTPUTS
FAN1 OFF/ON Fan 1 Relay
FAN2 OFF/ON Fan 2 Relay
FAN3 OFF/ON Fan 3 Relay
FAN4 OFF/ON Fan 4 Relay
FAN5 OFF/ON Fan 5 Relay
V.HPA XXX% Var Head Press % Cir A
V.HPB XXX% Var Head Press % Cir B
DIG.S XX sec Comp A1 Unload Time Range: 0 to 15 sec.
LSV.A OFF/ON Liquid Line Solenoid A
LSVA2 OFF/ON Liquid Line Solenoid A2
LSV.B OFF/ON Liquid Line Solenoid B
LSVB2 OFF/ON Liquid Line Solenoid B2
RMT.A OFF/ON Remote Alarm Relay
CMPA
CIRCUIT A COMPRESSOR TEST
CC.A1 OFF/ON Compressor A1 Relay
UL.TM XX sec Comp A1 Unload Time
Based on Unit Model
Range:
0 to 10 = 38AP025-030
0 to 8 = 38AP040-130
CC.A2 OFF/ON Compressor A2 Relay
CC.A3 OFF/ON Compressor A3 Relay
MLV OFF/ON Minimum Load Valve Relay
CMPB
CIRCUIT B COMPRESSOR TEST
CC.B1 OFF/ON Compressor B1 Relay
CC.B2 OFF/ON Compressor B2 Relay
CC.B3 OFF/ON Compressor B3 Relay