217
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Machine Control Type
MSV Point for i-Vu /
BACnet based on
CCN point
CTRLTYPE
R4
1 = VAV
2 = Invalid
3 = Tstat Multi
4 = Tstat 2 Stg
5 = SPT Multi
6 = Invalid
7 = PCT Cap
8 = Dual Tsat
9 = VAV Setpoint
MSV:3 ctrltype_msv_1
Machine Operating Hours HR_MACH R hr 0-9999 AV:57 mr_mach_1
Machine Starts CY_MACH R 0-9999 AV:58 cy_mach_1
Minimum Comp. On Time MODE_23 R ON_OFF BV:49 mode_23_1
Minimum Load Valve Relay MLV_RLY R ON_OFF BV:79 mlv_rly_1
Minimum OFF time active MODE_10 R ON_OFF BV:38 mode_10_1
Minutes Left for Start MIN_LEFT R min 00:00-15:00 AV:32 min_left_1
Minutes Off Time DELAY R/W min 0 0-15 AV:42 delay_1
Occupied OCC R YES_NO BV:2008 occ_status_1
Outside Air Temperature OAT R/W °F -40-245 AV:1003 oa_temp
Override Modes in Effect MODE R YES_NO BV:5 mode_1
Percent Available Cap. CAPA_A R % 0-100 AV:12 capa_a_1
Percent Available Cap. CAPB_A R % 0-100 AV:22 capb_a_1
Percent Total Capacity CAP_T R % 0-100 AV:3 cap_t_1
Percent Total Capacity CAPA_T R % 0-100 AV:11 capa_t_1
Percent Total Capacity CAPB_T R % 0-100 AV:21 capb_t_1
Ramp Load Limited MODE_5 R ON_OFF BV:33 mode_5_1
Requested Stage STAGE R 0-99 AV:9 stage_1
Return Air Temperature RETURN_T R °F 0-125 AV:1010 ra_temp_1
Saturated Condensing Tmp SCTA R °F -40-245 AV:40 scta_1
Saturated Condensing Tmp SCTB R °F -40-245 AV:39 sctb_1
Saturated Suction Temp SSTA R °F -40-245 AV:17 ssta_1
Saturated Suction Temp SSTB R °F -40-245 AV:26 sstb_1
SCT Delta for Compressor A1 A1SCTDT R/W °F 0-99 AV:41 a1sctdt_1
SCT Delta for Compressor A2 A2SCTDT R/W °F 0-99 AV:46 a2sctdt_1
SCT Delta for Compressor B1 B1SCTDT R/W °F 0-99 AV:47 b1sctdt_1
SCT Delta for Compressor B2 B2SCTDT R/W °F 0-99 AV:48 b2sctdt_1
Slow Change Override MODE_9 R ON_OFF BV:37 mode_9_1
Space T Cool Set Point SPT_SP R/W °F 78.0 0-999 AV:51 spt_sp_1
Space T SP Plus Offset SPSP_PO R/W °F 0-999 AV:76 spsp_po_1
Space Temp Control Mode SPTMODE R
0 = Cool Off
1 = Lo Cool
2 = Hi Cool
3 = Cool On
AV:52 sptmode_1
Space Temperature SPT R/W °F 0-999 AV:2007 space_temp
Space Temperature Offset SPTO R/W °F 0-99 AV:55 spto_1
Space Temperature Offset
Enable
SPTOSENS R/W ENA_DIS BV:10 sptosens_1
Space Temperature Offset
Range
SPTO_RNG R/W °F -20-99 AV:75 spto_rng_1
Space Temperature Sensor
SPTSENS R ENA_DIS BV:11 sptsens_1
Suction Pressure SP_A R psig 0-999 AV:14 sp_a_1
Suction Pressure SP_B R psig 0-999 AV:24 sp_b_1
Suction Superheat
Temperature
SH_A R °F -40-245 AV:44 sh_a_1
Suction Superheat
Temperature
SH_B R °F -40-245 AV:45 sh_b_1
Supply Air Set Point SAT_SP R °F 0-125 AV:78 sat_sp_1
Supply Air Temperature SUPPLY_T R °F -40-245 AV:1008 sa_temp_1
System Demand Limiting R Inactive_Active BV:83 dem_lmt_act_1
R—Read
W—Write