114
Table 40 — Capacity Staging, Staged Circuit Loading (Example)
UNIT CAPACITY STEP
LEAD CIRCUIT A LEAD CIRCUIT B
% DISPLACEMENT COMPRESSOR % DISPLACEMENT COMPRESSOR
38APD025-030
1 50A150B1
2 100 A1, B1 100 A1, B1
38APD040
1 26A124B1
2 53 A1, A2 47 B1, B2
3 76 A1, A2, B1 74 A1, B1, B2
4 100 A1, A2, B1, B2 100 A1, A2, B1, B2
38APD050
1 24A126B1
2 48 A1, A2 52 B1, B2
3 74 A1, A2, B1 76 A1, B1, B2
4 100 A1, A2, B1, B2 100 A1, A2, B1, B2
38APD060
1 23A127B1
2 46 A1, A2 54 B1, B2
3 73 A1, A2, B1 77 A1, B1, B2
4 100 A1, A2, B1, B2 100 A1, A2, B1, B2
38APD070
1 24A118B1
2 48 A1, A2 35 A1, B1
3 65 A1, A2, B1 52 A1, B1, B2
4 83 A1, A2, B1, B2 76 A1, A2, B1, B2
5 100 A1, A2, B1, B2, B3 100 A1, A2, B1, B2, B3
38APD080
1 20A120B1
2 40 A1, B1 40 A1, B1
3 60 A1, A2, B1 60 A1, B1, B2
4 80 A1, A2, B1, B2 80 A1, A2, B1, B2
5 100 A1, A2, B1, B2, B3 100 A1, A2, B1, B2, B3
38APD090
1 16A118B1
2 31 A1, A2 36 B1, B2
3 46 A1, A2, A3 54 B1, B2, B3
4 64 A1, A2, A3, B1 69 A1, B1, B2, B3
5 82 A1, A2, A3, B1, B2 85 A1, A2, B1, B2, B3
6 100 A1, A2, A3, B1, B2, B3 100 A1, A2, A3, B1, B2, B3
38APD100
1 17A117B1
2 33 A1, A2 33 B1, B2
3 50 A1, A2, A3 50 B1, B2, B3
4 67 A1, A2, A3, B1 67 A1, B1, B2, B3
5 83 A1, A2, A3, B1, B2 83 A1, A2, B1, B2, B3
6 100 A1, A2, A3, B1, B2, B3 100 A1, A2, A3, B1, B2, B3
38APD115
1 14A119B1
2 29 A1, A2 38 B1, B2
3 43 A1, A2, A3 57 B1, B2, B3
4 62 A1, A2, A3, B1 71 A1, B1, B2, B3
5 81 A1, A2, A3, B1, B2 86 A1, A2, B1, B2, B3
6 100 A1, A2, A3, B1, B2, B3 100 A1, A2, A3, B1, B2, B3
38APD130
1 13A121B1
2 25 A1, A2 42 B1, B2
3 38 A1, A2, A3 63 B1, B2, B3
4 58 A1, A2, A3, B1 75 A1, B1, B2, B3
5 79 A1, A2, A3, B1, B2 88 A1, A2, B1, B2, B3
6 100 A1, A2, A3, B1, B2, B3 100 A1, A2, A3, B1, B2, B3
38APS025-030
150A1
——
2 100 A1, A2
38APS040-050
133A1
——267A1, A2
3 100 A1, A2, A3
38APS065
1
——
33 B1
267B1, B2
3 100 B1, B2, B3