APPENDIX B — CCN TABLES (cont)
Maintenance Tables (cont)
LEARNFNS
LOADFACT (Capacity Control)
PM-COIL (Condenser Coil Preventative Maintenance)
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
SCT Delta for Comp A1 NNN.N 'F ('C) A1SCTDT Read Only
SCT Delta for Comp A2 NNN.N 'F ('C) A2SCTDT Read Only
SCT Delta for Comp B1 NNN.N 'F ('C) B1SCTDT Read Only
SCT Delta for Comp B2 NNN.N 'F ('C) B2SCTDT Read Only
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
CAPACITY CONTROL
Load/Unload Factor NNN SMZ Read Only
Control Point NNN.n °F (°C) CTRL_PNT Read/Write
Return Air Temperature NNN.n °F (°C) RETURN_T Read/Write
Supply Air Temperature NNN.n °F (°C) SUPPLY_T Read/Write
Ramp Load Limited OFF/ON MODE_5 Read Only
Slow Change Override OFF/ON MODE_9 Read Only
Low Temperature Cooling OFF/ON MODE_17 Read Only
High Temperature Cooling OFF/ON MODE_18 Read Only
Minimum Comp. On Time OFF/ON MODE_23 Read Only
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
Coil Cleaning Srvc Inter
NNNNN
Range: 0 to 65,500
Default: 8760
hours SI_COIL Read/Write
Coil Service Countdown NNNNN hours CL_CDOWN Read Only
Coil Cleaning Maint.Done NO/YES CL_MAINT Read Write
Coil Cleaning Maint.Date 00/00/00 00:00 COIL_PM0 Read Only
Coil Cleaning Maint.Date 00/00/00 00:00 COIL_PM1 Read Only
Coil Cleaning Maint.Date 00/00/00 00:00 COIL_PM2 Read Only
Coil Cleaning Maint.Date 00/00/00 00:00 COIL_PM3 Read Only
Coil Cleaning Maint.Date 00/00/00 00:00 COIL_PM4 Read Only