3.13 - Multiple chiller installation
It is recommended to install multiple chillers in a single row,
arranged as shown in the example below, to avoid recycling of
warm air from one unit to another.
1.5 m
mini
1,5 m
mini
If the situation at the site does not permit this arrangement, contact
your Carrier distributor to evaluate the various possible
arrangements. In certain situations an accessory (supplied loose
at the time of purchase) can be added.
3.14 - Distance to the wall
To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your Carrier distributor to evaluate the
various possible arrangements. In certain situations an accessory
(supplied loose at the time of purchase) can be added.
H
S
h
Anti-vibration
mounts
1.5 m
1.5 m
min.
min.
3 - DIMENSIONS, CLEARANCES