EasyManua.ls Logo

Carrier AquaForce 30XB series - Page 24

Carrier AquaForce 30XB series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
4.1 - Physical data 30XBP (continued)
30XBP-850 to 1500 (continued)
30XBP 850 900 1000 1100 1200 1300 1400 1500
Capacity control Touch Pilot, , Electronic Expansion Valve (EXV)
Minimum capacity % 15 15 15 15 15 15 15 15
Air heat exchanger Aluminum micro-channel coils (MCHE)
Fans FLYING-BIRD 6, axial fan with rotating impeller
Standard unit
Quantity 14 14 16 20 20 20 20 22
Maximum total air ow l/s 67480 67480 77120 96400 96400 96400 96400 106040
Maximum rotation speed r/s 15,7 15,7 15,7 15,7 15,7 15,7 15,7 15,7
Unit + option 15LS
Maximum total air ow l/s 55020 55020 62880 78600 78600 78600 78600 86460
Maximum rotation speed r/s 11,7 11,7 11,7 11,7 11,7 11,7 11,7 11,7
Water heat exchanger Flooded multi-pipe type
Water volume l 119 130 140 164 174 180 189 189
Max. water-side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option) Pump, Victaulic screen lter, relief valve, water and air drain valve,
pressure sensors, expansion tank (option)
Pump Centrifugal pump, monocell, 48,3r/s, low or high pressure (as required), single or dual
(as required)
Expansion vessel volume inch
Max. water-side operating pressure with hydraulic module mm
Water connections without or with hydraulic module Victaulic
®
type
Connections inch 6 6 8 6 6 6 6 6
External parameter
(5)
mm 168,3 168,3 219,1 168,3 168,3 168,3 168,3 168,3
Casing paint Colour code RAL 7035
(5) Depends of options.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS

Table of Contents

Related product manuals