27
4.3 - Physical data 30XB with option 254 or 255 (continued)
30XB-850 to 1700 with option 254 or 255
30XB option 254/255 850 900 1000 1100 1200 1300 1400 1550 1700
Sound levels
Standard unit
Sound power
(1)
dB(A) 101 104 102 103 102 104 104 104 104
Sound pressure at 10 m
(2)
dB(A) 70 71 69 70 69 71 71 71 70
Unit + option 15
(3)
Sound power
(1)
dB(A) 97 99 98 98 98 100 99 100 100
Sound pressure at 10 m
(2)
dB(A) 65 66 65 65 65 67 65 67 66
Unit + option 15LS
(3)
Sound power
(1)
dB(A) 94 95 94 94 94 99 95 96 96
Sound pressure at 10 m
(2)
dB(A) 60 62 65 65 61 65 61 61 61
Unit + option 15LS+
(3)
Sound power
(1)
dB(A) 91 93 92 93 93 97 94 93 93
Sound pressure at 10 m
(2)
dB(A) 58 60 59 60 60 66 61 60 60
Dimensions
Standard unit
Length mm 8380 9574 9574 11962 11962 11962 11962 9574/
4798
8380/
8380
Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height mm 2297 2297 2297 2297 2297 2297 2297 2297 2297
Operating weight
(4)
Standard unit kg 6414 7049 7253 8628 8761 9339 9416 3716/
7287
6464/
6464
Unit + option 15
(3)
kg 6745 7380 7584 8999 9132 9711 9788 3882/
7618
6794/
6794
Compressors 06T semi-hermetic screw compressor, 50 r/s
Circuit A 1 1 1 1 1 1 1 1 1
Circuit B 1 1 1 1 1 1 1 1 1
Circuit C 1 1
Circuit D 1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A kg 130 129 140 125 128 170 176 140 130
teqCO
2
185,9 184,5 200,2 178,8 183,0 243,1 251,7 200,2 185,9
Circuit C kg 95 103 129 180 196 176 184 129 95
teqCO
2
135,9 147,3 184,5 257,4 280,3 251,7 263,1 184,5 135,9
Circuit B kg 135,0 130,0
teqCO
2
193,1 185,9
Circuit D kg 95,0
teqCO
2
135,9
Oil
Circuit A l 27,6 27,6 27,6 27,6 36,0 36,0 36,0 27,6 27,6
Circuit B l 23,5 27,6 27,6 36,0 36,0 36,0 36,0 27,6 23,5
Circuit C l 27,6 27,6
Circuit D l 23,5
(1) in dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certied by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified
values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS