20
circuit’s capacity is limited and that eventually the circuit may
shut down.
Time, Day, and Date — Many features of the 30MP
controls require that the time, day and date be properly set.
This is especially helpful when troubleshooting alarms, as they
are reported with a time and date stamp. ComfortLink controls
also have the ability to automatically adjust for daylight sav-
ings time, when configured. The unit time and date is set at the
factory based in the Eastern Time Zone.
To set the time, Time Clock
TIME
HH.MM (Hour and
Minute) is the item. The time clock is programmed in a 24-
hour format, 00.00 to 23.59. See Table 15.
To set the month, Time Clock
DATE
MNTH (Month)
is the item. This item follows the standard convention, 1=Janu-
ary, 2=February, etc.
To set the day of the month, Time Clock
DATE
DOM
(Day of Month) is the item.
To set the day of the week, Time Clock
DATE
DAY
(Day of Week) is the item. This item uses the following con-
vention: 1=Monday, 2=Tuesday, 3=Wednesday, etc. This set-
ting is important if using the internal schedule.
To set the year, Time Clock
DATE
YEAR (Year of Cen-
tury) is the item. This item follows the convention of a 4-digit
year, such as 2014.
Table 16 lists the required configurations for these settings.
TIME/DATE BROADCAST The 30MP unit controls
have the ability to broadcast the time and date on the network.
If the CCN Time/Date Broadcast configuration Configura-
tion
BCST
T.D.BC=ON, the control will send the time and
date out onto the CCN bus once a minute. If this device is on a
CCN network, it is important to make sure that only one
device on the bus has this configuration set to ON. If more
than one time broadcaster is present, problems with the time
will occur. If the unit is installed on a network, another unit
must be configured to be Broadcast Acknowledger, Configu-
ration
BCST
BC.AK. Only one unit can be the Broadcast
Acknowledger. See Table 17 for required configurations.
DAYLIGHT SAVINGS TIME — The 30MP controls have
the ability to automatically adjust the time for daylight savings
time. To utilize this feature, several items must be configured,
including a start date and time to add as well as an end date.
All items are found in the Daylight Saving Time sub-mode,
Time Clock
DST and the Broadcast sub-mode, Configura-
tion
BCST. See Table 18 for required configurations.
NOTE: Only the time and date broadcaster can perform day-
light savings time adjustments. Even if the unit is stand-alone,
the user may want to set Configuration
BCST
T.D.BC to
ON to accomplish the daylight savings function. To disable the
daylight savings time feature, set T.D.BC to OFF.
Table 15 — Time Required Configuration
Table 16 — Day and Date Required Configurations
Table 17 — Broadcast Required Configurations
*Only the time and date broadcaster can perform daylight savings
time adjustments. Even if the unit is stand-alone, the user may want
to set this to ON to accomplish the daylight savings function.
TIME CLOCK MODE
SUBMODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
TIME HH.MM XX.XX Hour and Minute
24-hour format
Range: 00.00 to 23.59
TIME CLOCK MODE
SUBMODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
DATE
MNTH XX Month of Year
Range: 1-12
(1=January, 2=February, etc.)
DOM XX Day of Month Range: 1-31
DAY X Day of Week
Range: 1-7
(1=Monday, 2=Tuesday, etc.)
YEAR XXXX Year of Century
CONFIGURATION MODE
SUBMODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
BCST
T.D.BC ON/OFF CCN Time/Date Broadcast
Default: Off
Must be set to ON to enable automatic
Daylight Savings Time correction.*
BC.AK ON/OFF CCN Broadcast Ack'er
Default: Off
One unit on the network must be set to
ON. The broadcast unit cannot be the
acknowledger.