Carrier AquaSnap 30MPA Series - Configuring Demand Limit

Carrier AquaSnap 30MPA Series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
Table 31 — Configuring Demand Limit
*Seven items skipped in this example.
MODE
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION
DISP TEST ON/OFF Test Display LEDs
UNIT TYPE X Unit Type
OPT1 FLUD X Cooler Fluid
OPT2 CTRL X Control Method
CCN
CCNA X CCN Address
EXV.A
RSET CRST X Cooling Reset Type
DMDC* X Demand Limit Select
Default: 0
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
DM20 XXX % Demand Limit at 20 mA
Default: 100%
Range: 0 to 100
SHNM XXX
Loadshed Group
Number
Default: 0
Range: 0 to 99
SHDL XXX%
Loadshed Demand
Delta
Default: 0%
Range: 0 to 60%
SHTM XXX MIN
Maximum Loadshed
Time
Default: 60 min.
Range: 0 to 120 min.
DLS1 XXX %
Demand Limit
Switch 1
Default: 80%
Range: 0 to 100%
DLS2 XXX %
Demand Limit
Switch 2
Default: 50%
Range: 0 to 100%
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
90
(32)
80
(27)
70
(21)
60
(15)
50
(10)
40
(4.4)
30
(–1)
20
(–7)
10
(–12)
0
(–17)
0
5
10
15 20
25
mA Signal
Set Point, F (C)
FLUD=1 (Water)
Minimum Set Point
38 F (3.3 C)
Maximum Set Point
70 F (21.1 C)
FLUD=2 (Medium Temp Brine)
Minimum Set Point
14 F (–10.0 C)
Fig. 24 — Cooling Set Point (4 to 20 mA)
EMM Energy Management Module