Table 24 — Control Methods and Cooling Set Points
* Energy management module (EMM) required for operation.
† Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.
Control Type
(CTRL)
CCN Chiller
CHIL_S_S
Set Point Select
(CLSP)
Ice Mode
(ICE.M)*
Ice Done Status
(ICED)*
Dual Set Point
Switch (DUAL)
Occupancy
State
(OCC)
Active Set
Point
(SETP)
0 (Switch)
0 (Single) CSP.1
1 (Dual Switch)†
OFF CSP.1
ON CSP.2
ENBL
OFF CSP.1
ON ON CSP.2
OFF ON CSP.3
2 (Dual CCN
Occupied)
YES CSP.1
NO CSP.2
ENBL
YES CSP.1
ON NO CSP.2
OFF NO CSP.3
3 (4 to 20 mA
Input)*
4-20 mA
1 or 2
(Occupancy)
0 (Single)
YES CSP.1
—— NOOff
1 (Dual Switch)†
OFF YES CSP.1
ON YES CSP.2
—— NOOff
ENBL
OFF YES CSP.1
ON YES CSP.2
——NOOff
2
(Dual CCN
Occupied)
Illegal
3 (4 to 20 mA
Input)*
YES 4-20 mA
—— NOOff
3 (CCN)
Stop Off
Start
0 (Single) CSP.1
1 (Dual Switch)†
OFF CSP.1
ON CSP.2
ENBL
OFF CSP.1
ON ON CSP.2
OFF ON CSP.3
2 (Dual CCN
Occupied)
YES CSP.1
NO CSP.2
ENBL
YES CSP.1
ON NO CSP.2
OFF NO CSP.3
3 (4 to 20 mA
Input)*
4-20 mA
DESCRIPTION STATUS POINT
Alarm Routing 0 0 0 0 0 0 0 0 ALRM_CNT
Building Supervisor,
ComfortVIEW™,
ComfortWORKS
,
BACnet Communications (UPC),
BACnet Translator
TeLink,
Autodial Gateway
Unused
Alarm Printer interface Module,
BACLink or DataLINK™
Unused
Fig. 16 — Alarm Routing Control