APPENDIX B — CCN TABLES (cont)
CCN SERVICE TABLES
CCN SETPOINT TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SERVICE SERVICE
Brine Freeze Point NNN.n degF BRN_FRZ 34.0
COMPRESSOR ENABLE
Enable Compressor A1 Disable/Enable ENABLEA1 Unit Dependent
Enable Compressor A2 Disable/Enable ENABLEA2 Unit Dependent
Enable Compressor A3 Disable/Enable ENABLEA3 Unit Dependent
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SETPOINT SETPOINT
COOLING
Cooling Setpoint 1 NNN.n degF CSP1 44.0
Cooling Setpoint 2 NNN.n degF CSP2 44.0
ICE Setpoint NNN.n degF CSP3 32.0
RAMP LOADING
Cooling Ramp Loading N.n CRAMP 1.0
Brine Freeze Point NNN.n degF BRN_FRZ 34.0