APPENDIX A — LOCAL DISPLAY TABLES (cont)
Service Test Mode and Sub-Mode Directory
ITEM EXPANSION RANGE UNITS CCN POINT COMMENT
TEST SERVICE TEST MODE OFF/ON MAN_CTRL To enable Service Test
mode, move Enable/Off/
Remote control switch to
OFF. Change TEST to
ON. Move switch to
ENABLE.
OUTS OUTPUTS AND PUMPS
CLR.P Cooler Pump Relay OFF/ON S_CLPMP
CND.P Condenser Pump OFF/ON S_CNDPMP
UL.TM Comp A1 Unload Time 0 to 15 xx S_A1ULTM
CC.H Crankcase Heater OFF/ON S_CCH
CW.VO Condenser Valve Open OFF/ON S_CWVO not supported
CW.VC Condenser Valve Close OFF/ON S_CWVC not supported
EXV.A EXV% Open xxx% S_EXV_A
LL.SV Liquid Line Solenoid OFF/ON S_LLSV
RMT.A Remote Alarm Relay OFF/ON S_ALM
CMPA CIRCUIT 1 COMPRESSOR TST
CC.A1 Compressor A1 Relay OFF/ON S_A1_RLY
UL.TM Comp A1 Unload Time 0 to 15 xx S_A1ULTM
CC.A2 Compressor A2 Relay OFF/ON S_A2_RLY
CC.A3 Compressor A3 Relay OFF/ON S_A3_RLY
MLV Minimum Load Valve Relay OFF/ON S_MLV