APPENDIX A — LOCAL DISPLAY TABLES (cont)
Outputs Mode and Sub-Mode Directory (cont)
Configuration Mode and Sub-Mode Directory
ITEM EXPANSION UNITS CCN POINT COMMENT
CIR.A OUTPUTS CIRCUIT A
CC.A1 Compressor A1 Relay OFF/ON K_A1_RLY
D.PER Compressor A1 Load Percent OFF/ON DIGITALP
CC.A2 Compressor A2 Relay OFF/ON K_A2_RLY
CC.A3 Compressor A3 Relay OFF/ON K_A3_RLY
CCH Crankcase Heater Relay OFF/ON CCH_RLY
LLSV Liquid Line Solenoid OFF/ON LLSV_A
MLV.R Minimum Load Valve Relay OFF/ON MLV_RLY
A.EXV
EXV.A EXV% Open OFF/ON EXV_A
APPR Circuit A Approach OFF/ON CIRA_APP
AP.SP Approach Setpoint OFF/ON APPRA_SP
X.SH.R SH Reset at Max Unl-Dig MAXSHRST
S.SH.R Digload to Start SH RST SHRSTBGN
SH_R Amount of SH Reset SH_RESET
OVR.A EXVA Override OFF/ON EXVAOVRR
SPH.A Suction Superheat Temp OFF/ON SH_A
ASH.S Active Superheat Setpt OFF/ON ACTSH_SP
AMP.S Active Mop Setpt OFF/ON ACMOP_SP
PLM.A Cir A EXV Position Limit OFF/ON PLMA
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs OFF/ON DISPTEST
METR Metric Display OFF = English
ON = Metric
DISPUNIT OFF = English
LANG Language Selection 0 = English
1 = Espanol
2 = Francais
3 = Portuguese
X LANGUAGE 0
PAS.E Password Enable DSBL/ENBL PASS_EBL ENBL
PASS Service Password 0 to 9999 XXXX PASSCOPY 1111
UNIT UNIT CONFIGURATION
TYPE Unit Type
2=Air Cooled,
3=Water Cooled
XUNIT_TYP
SIZE Unit Size 15 to 74 XXX SIZE
SZA.1 Compressor A1 Size Unit Size Depen-
dent
XX SIZE_A1
SZA.2 Compressor A2 Size Unit Size Depen-
dent
XX SIZE_A2
SZA.3 Compressor A3 Size Unit Size Depen-
dent
XX SIZE_A3
A1.TY Compressor A1 Digital? NO/YES CPA1TYPE
MAX.T Maximum A1 Unload Time 0 to 15 XX MAXULTME 7 (040,045)
10 (020,030)
D.TYP Discharge Gas Therm Type 0 = 86K
1 = 100K
X DGASTYPE 0
OPT1 UNIT OPTIONS 1 HARDWARE
FLUD Cooler Fluid
1 = Water
2 = Medium Temp
Brine
X FLUIDTYP 1 = Water
MLV.S Minimum Load Vlv Select NO/YES MLV_FLG NO
RG.EN Return Gas Sensor Enable DSBL/ENBL RGT_ENA
OAT.E Enable OAT Sensor DSBL/ENBL OAT_ENA
CSB.E CSB Boards Enable DSBL/ENBL CSB_ENA
CPC Cooler Pump Control OFF/ON CPC ON
PM.DY Cooler Pump Shutdown Dly 0 to 10 XX MIN PUMP_DLY 1 MIN
D.PM.E Enable Condenser Pump 0=No Control
1=On When Occu-
pied
2=On with Com-
pressors
X CONDPMPE 0=No Control
D.FL.S Enable Cond Flow Switch DSBL/ENBL CONDFLSW DSBL
CDWS Enable Cond Wtr Sensors DSBL/ENBL CONDWTRS DSBL
OPT2 UNIT OPTIONS 2 CONTROLS
CTRL Control Method 0=Switch
1=Occupancy
2=Occupancy
3=CCN
XCONTROL0=Switch
LCWT High LCW Alert Limit 2 to 60°F XX LCW_LMT 60°F
DELY Minutes Off Time 0 to 15 XX DELAY 0
ICE.M Ice Mode Enable DSBL/ENBL
(Requires EMM)
ICE_CNFG DSBL