APPENDIX A — LOCAL DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
EXV.A CIR A EXV CONFIGURATION
EXV.L EXV Opening at Low LWT
0 to 50%
XX% 25%
LWT.L LWT for EXV Min Opening
20 to 40 F
XX° F 10 F
EXV.H EXV Opening at High LWT
0 to 70%
XX% 50%
LWT.H LWT for EXV Max Opening
20 to 70 F
XX° F 35 F
MIN.A EXV CIRC.A Min Position
0 to 100
XXX 2
RNG.A EXVA Steps in Range
0 to 65535
XXXXX 3690
SPD.A EXVA Steps Per Second
0 to 65535
XXXXX 150
POF.A EXVA Fail Position In%
0 to 100
XXX 0
MIN.A EXVA Minimum Steps
0 to 65535
XXXXX 0
MAX.A EXVA Maximum Steps
0 to 65535
XXXXX 3690
OVR.A EXVA Overrun Steps
0 to 65535
XXX 167
TYP.A EXVA Stepper Type 0 = UNIPOLAR
1 = BIPOLAR
0,1 1
H.SCT High SCT Threshold
50 to 140
XXX 115
X.PCT Open EXV X% on 2nd COMP
0 to 30
XX 10
X.PER Move EXV X% on DISCRSOL
0 to 30
XX 5
DELY Lag Start Delay
0 to 100
XXX 10
L.DL.T Low SH Delta T - EXV Move
0 to 240
XXX 6
SHR.T EXV Rate Threshold
–1.0 to 1.0F
XX.X F 0.2F
LEXM Low SH Override EXV Move
0.4 to 3.0
X.X% 1.0%
CCN CCN NETWORK CONFIGS
CCNA CCN Address 1 to 239 XXX CCNADD 1
CCNB CCN Bus Number 0 to 239 XXX CCNBUS 0
BAUD CCN Baud Rate 1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
X CCNBAUDD 3 = 9600
RSET
RESET COOL TEMP
CRST Cooling Reset Type 0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air
Temp
3 = Return Fluid
4 = Space Temp
X
CRST_TYP 0 = No Reset
MA.DG 4-20 - Degrees Reset –30 to 30F XX.XΔF MA_DEG 10.0F
RM.NO Remote - No Reset Temp 0 to 125°F XXX.X °F REM_NO 10.0F
RM.F Remote - Full Reset Temp 0 to 125°F XXX.X °F REM_FULL 0.0F
RM.DG Remote - Degrees Reset –30 to 30F
XX.X ΔF
REM_DEG 0.0F
RT.NO Return - No Reset Temp 0 to 30F XXX.XΔF RTN_NO 10F
RT.F Return - Full Reset Temp 0 to 10F XXX.XΔF RTN_FULL 0.0F
RT.DG Return - Degrees Reset –30 to 30F
XX.XΔF
RTN_DEG 0.0F
DMDC Demand Limit Select 0 = None
1 = Switch
(Requires EMM)
2 = 4 to 20 mA Input
(Requires EMM)
3 = CCN Loadshed
X
DMD_CTRL 0 = None
DM20 Demand Limit at 20 mA 0 to 100 XXX% DMT20MA 100
SHNM Loadshed Group Number 0 to 99 XXX SHED_NUM 0
SHDL Loadshed Demand Delta 0 to 60 XXX% SHED_DEL 0
SHTM Maximum Loadshed Time 0 to 120 XXX SHED_TIM 60
DLS1 Demand Limit Switch 1 0 to 100 XXX% DLSWSP1 80
DLS2 Demand Limit Switch 2 0 to 100 XXX% DLSWSP2 50
LLEN Lead/Lag Chiller Enable DSBL/ENBL LL_ENA DSBL
MSSL Master/Slave Select SLVE/MAST MS_SEL MAST
SLVA Slave Address 0 to 239 XXX SLV_ADDR 0
LLBL Lead/Lag Balance Select 0 = Master Leads
1 = Slave Leads
2 = Automatic
X LL_BAL 0 = Master Leads
LLBD Lead/Lag Balance Delta 40 to 400 hours XXX LL_BAL_D 168
LLDY Lag Start Delay 0 to 30 minutes XXX LL_DELAY 5 minutes
PARA Parallel Configuration NO/YES PARALLEL YES