APPENDIX D — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
30MP Monthly Maintenance Log
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
Month 123456789101112
Date / / / / / / / / / / / / / / / / / / / / / / / /
Operator
UNIT
SECTION
ACTION UNIT ENTRY
Compressor
Check Oil Level yes/no
Leak Test yes/no
Cooler
Inspect and Clean Cooler yes/no
Every 3 - 5 Years
Inspect Cooler Heater amps
Leak Test yes/no
Record Water Pressure Differential (PSI) PSI
Inspect Water Pumps yes/no
Condenser
Leak Test yes/no
Inspect and Clean Condenser Coil yes/no
Controls
General Cleaning and Tightening Connections yes/no
Annually
Check Pressure Transducers yes/no
Confirm Accuracy of Thermistors yes/no
Starter
General Tightening and Cleaning Connections yes/no
Annually
Inspect All Contactors yes/no
System
Check Refrigerant Charge yes/no
Verify Operation of EXVs and Record Position 0-100%
Record System Superheat deg. F