60
POWER_O 11H 10 //MAINMENU/MAINTAIN/
30 stat_wd 0 - VFD Status Word
31 cmd_wd 0 - VFD Command Word
32 str_inh 0 - VFD Start Inhibit Status
33 appl_do 0 - VFD Appl digital Output
34 safestop 0 to 1 0 - Safety Stop Status 0 1
35 spd_fd 0 to 1 0 - SPD Feedback 0 1
36 VFDC_HI no/yes - High VFD Current
ALARMRST 12H 1 //MAINMENU/ALARM/
1 RST_ALM 0 to 1 - Alarm Reset 0 1 x
2 ALM_STAT - Alarm State
3 alarm_1c - Current Alarm 1
4 alarm_2c - Current Alarm 2
5 alarm_3c - Current Alarm 3
6 alarm_4c - Current Alarm 4
7 alarm_5c - Current Alarm 5
8 alarm_1 - Jbus Current Alarm 1
9 alarm_2 - Jbus Current Alarm 2
10 alarm_3 - Jbus Current Alarm 3
11 alarm_4 - Jbus Current Alarm 4
12 alarm_5 - Jbus Current Alarm 5
CAPACTRL 12H 2 //MAINMENU/MAINTAIN/
1 tot_err ^F Total Error + Resets
2 ctrl_err ^F Control Point Error
3 ctrl_wt °F Controlled Water Temp
4 ctrl_pnt °F Control Point
5 setpoint °F Actual Setpoint
6 ewt_dt ^F Entering Water Change DT
7 ewt_res ^F Enter Water Temp Reset
8 lwt_res ^F Leaving Water Temp Reset
9 dgt_res ^F Discharge Gas Temp Reset
10 capa_dlt % Capacity Delta
11 gv1_tgt % Target GV1 Pos
12 gv1delta % GV1 Pos Change Delta
13 gv1_chg - GV1 Change Flag
14 - Stop=0, Change=1, Cont=2
15 vfd_chg - VFD Speed Change Flag
16 - Stop=0, Change=1, Cont=2
17 vfd_tgt % Target VFD Speed Per
18 vfd_dlta % VFD Speed Change Delta
19 hgbp_tp % EC Valve Target Percent
20 cap_inh no/yes - Capacity Inhibit Flag
21 cap_dec no/yes - Capacity Decrease Flag
22 cdw_dt ^F Condenser Water Delta T
23 chw_dt ^F Chilled Water Delta T
24 pull_set °F Pulldown Set Point
25 deinhclm % Demand Limit Inh Clamp
26 ramp_dem % Ramping Demand Limit Val
27 comp_run no/yes - Compressor is Running
28 cm_stat1 - Comp1 Run State Val