OVERRIDE 12H 3 //MAINMENU/MAINTAIN/
     








1 cap_inho no/yes - Capacity Inhibit
2 cap_deco no/yes - Capacity Decrease
3 cpov_ no/yes - High Condenser Pressure
4 dshov_ no/yes - Low Discharge Superheat
5 sstov_ no/yes - Low Suction Sat Temp
6 mtov_ no/yes - High Motor Temp
7 tbov_ no/yes - High Bearing Temp
8 lstov_ no/yes - Low Source Temp
9 dgtov_ no/yes - High Discharge Temp
10 ampov_ no/yes - High Motor Current
11 dsh_req ^F Required DSH
12 ert_over °F Evap Sat Override Temp
13 dshinstp % IGV Step DSH Increase
14 dshdestp % IGV Step DSH Decrease
15 cp_trip PSIG Cond Press Trip Value
   
MAISURGE 12H 4 //MAINMENU/MAINTAIN/
     








1 act_reg - Surge Region
2 - No=0, Low=1, High=2
3 - Deadband=3, Noise=4
4 dts_act ^F Actual Delta Tsat
5 dts_cal ^F Calc Ref Delta Tsat
6 dts_he ^F High E Ref Delta Tsat
7 amps_dta % Amps Change Surge Prot
8 amch_max % Max Amps Change Value
9 sc - Surge Counts
10 spc - Surge Protection Counts
11 surg_act no/yes - Surge Prevention Active
12 surg_pro no/yes - Surge Protection Active
13 hgbp_chg - EC Valve Change Flag
14 - Close=0, Hold=1, Open=2
15 dts_maxc 0.0 to 150.0 ^F Cal Surge Delta Tsmax 0 150
16 dts_minc 0.0 to 150.0 ^F Cal Surge Delta Tsmin 0 150
17 dts_medc 0.0 to 150.0 ^F Cal Surge Delta Tsmed 0 150
18 gv1_sful 0.0 to 100.0 % IGV1 Full Load Position 0 100
19 gv1_smin 0.0 to 100.0 % IGV1 Minimum Position 0 100
20 gv1_smed 0.0 to 100.0 % Opti-Sound IGV1 Position 0 100
21 enlp_opt 0 to 1 - Envelope Line Optimized 0 1
   
QCK_TEST 12H 5 //MAINMENU/
     








1 QCK_TEST 0 to 1 0 0 to 1 Quick Test Enable 0 1 x
2 Q_OILH 0 to 1 0 0 to 1 Quick Test Oil Heater 0 1 x
3 Q_OILP 0 to 1 0 0 to 1 Quick Test Oil/Ref Pump 0 1 x
4 OP_PASS 0 to 1 0 0 to 1 Oil/Ref Pres Test Passed 0 1
5 OIL_PDQ Oil/Ref Pump Delta Press
6 Q_EXV 0 to 100 0 0 to 100 Quick Test Oil EXV 0 100 x
7 Q_HDP 0 to 100 0 0 to 100 Quick Test Head Val Pos 0 100 x
8 Q_CHST 4 to 20 4 4 to 20 Quick Test Chiller Stat 4 20 x
9 Q_GV1POS 0 to 100 0 0 to 100 Guide Vane 1 Tested Pos 0 100 x
10 Q_GV2POS 0 to 100 0 0 to 100 Guide Vane 2 Tested Pos 0 100 x
11 Q_GV1OP 0 to 1 0 0 to 1 Quick Test GV1 Open 0 1 x
12 Q_GV1CL 0 to 1 0 0 to 1 Quick Test GV1 Close 0 1 x
13 Q_GVSRD 0 to 1 0 0 to 1 GV1/SRD Joint Test 0 1 x
14 Q_SRD 0 to 100 0 0 to 100 Quick Test Diuser Pos 0 100 x
15 Q_GV1ACT Guide Vane 1 Actual Pos
16 Q_DIFTGT Diuser Target Pos
17 Q_HGBPOP 0 to 1 0 0 to 1 Quick Test ECV Open 0 1 x
18 Q_HGBPCL 0 to 1 0 0 to 1 Quick Test ECV Close 0 1 x
19 Q_HGBP_T 0 to 100 0 0 to 100 EC Valve Tested Pos 0 100 x