65
MAIOTHER 12H 12 //MAINMENU/
23 op_prest no/yes - Oil Pump Req Prestart
24 pump_srt no/yes - Pump Req Startup
25 pump_sht no/yes - Pump Req Shutdown
26 pump_rst no/yes - Pump Req Swift Rst
27 ep_start no/yes - Evap Pump Req Startup
28 ep_diag no/yes - Evap Pump Req Diagnostic
29 ep_freze no/yes - Evap Pump Req Frozen
30 ep_shut no/yes - Evap Pump Req Shutdown
31 ep_pdown no/yes - Evap Pump Req Pumpdown
32 cp_prest no/yes - Cond Pump Req Prestart
33 cp_start no/yes - Cond Pump Req Startup
34 cp_overr no/yes - Cond Pump Req Override
35 cp_shut no/yes - Cond Pump Req Shutdown
36 cp_tower no/yes - Cond Pump Req Tower
37 co_diag no/yes - Cond Pump Req Diagnostic
38 cp_freze no/yes - Cond Pump Req Frozen
39 cp_pdown no/yes - Cond Pump Req Pumpdown
40 cap_inhr no/yes - Capacity Inhibit Ramping
41 cap_inhd no/yes - Capacity Inhibit Demand
42 cap_decd no/yes - Capacity Decrease Demand
43 gv1_inhs no/yes - Guide Vane Inh Surge
44 cap_decs no/yes - Capacity Decrease Surge
45 capinhst no/yes - Capacity Inh Low SST
46 capdecst no/yes - Capacity Dec Low SST
47 capinhcp no/yes - Capacity Inh Cond Pres
48 capdeccp no/yes - Capacity Dec Cond Pres
49 capinhmt no/yes - Capacity Inh Motor Temp
50 capdecmt no/yes - Capacity Dec Motor Temp
51 capinham no/yes - Capacity Inh Hi Current
52 capdecam no/yes - Capacity Dec Hi Current
53 capdecls no/yes - Capacity Dec Low Temp
54 gv2posok no/yes - GV2 Pos at Startup OK
ISM_MCFG 12H 13 //MAINMENU/MAINTAIN/
1 ism_ct 0 to 1 0 - ISM Cong Conict 0 1
2 del_ismc 0 to 1 0 - Delete ISM Cong 0 1 x
3 com_tout 0 to 255 60 sec Communication Timeout 0 255
4 star_typ 0 to 3 0 - Starter Type 0 3
5 - Full Volt=0, Redu Volt=1
6 - Solid State=2, FS VFD=3
7 scycd_en 0 to 1 0 - Single Cycle Dropout 0 1
8 rla 10 to 5000 200 AMPS Motor Rated Load Amps 10 5000
9 mot_lra 100 to 65535 1000 AMPS Motor Locked Rotor Trip 100 65535
10 lrs_del 1 to 10 5 cycles Locked Rotor Start Delay 1 10
11 str_lra 100 to 65535 2000 AMPS Starter LRA Rating 100 65535
12 rlv 200 to 13800 460 Volts Motor Rated Line Voltage 200 13800
13 cu_th 5 to 100 15 % Current Imbal Threshold 5 100
14 vu_th 1 to 10 5 % Voltage Imbal Threshold 1 10
15 ct_ratio 3 to 1000 100 - Motor Current CT Ratio:1 3 1000
16 vt_rat 1 to 115 1 - Volt Transformer Ratio:1 1 115
17 cu_per 1 to 10 5 sec Current Imbal Persist 1 10
18 vu_per 1 to 10 5 sec Voltage Imbal Persist 1 10
19 lfref_en 0 to 1 0 - Line Frequency Faulting 0 1
20 linefreq 0 to 1 0 - Frequency(N=50Hz Y=60Hz) 0 1
21 gfp_en 0 to 1 1 - Ground Fault Protection 0 1
22 gf_amps 1 to 25 15 AMPS Ground Fault Current 1 25
23 gfp_pers 1 to 10 5 cycles Ground Fault Persistence 1 10
24 gfs_del 1 to 20 10 cycles Ground Fault Start Delay 1 20
25 gfct_rat 150 to 150 150 - Ground Fault CT Ratio:1 150 150
26 ovvol_th 105 to 115 115 % Overvoltage Threshold 105 115
27 udvol_th 85 to 95 85 % Undervoltage Threshold 85 95
28 ovud_per 1 to 10 5 sec Over Under Volt Persist 1 10
29 uvs_del 1 to 4 1 sec Under Volt Start Delay 1 4