CFGSURGE 13H 7 //MAINMENU/CONFIG
1 sgl_cfg 0 to 1 0 - Surge Line Conguration 0 1
2 - PR = 0, Delta T = 1
3 gv1c_sel 0 to 1 0 - IGV1 Pos Conguration 0 1
4 - Degree =0, Percentage =1
5 dts_max 0.0 to 150.0 70 ^F Surge Delta Tsmax 0 150
6 dts_min 0.0 to 150.0 45 ^F Surge Delta Tsmin 0 150
7 pr_ful 1.0000 to 5.0000 3 - PR at Full Load Opening 1 5
8 pr_min 1.0000 to 5.0000 1.5 - PR at Minimum Opening 1 5
9 gv1_dful 80 to 120.0 88 - IGV1 Full Load Open Deg 80 120
10 gv1_dmed 10.0 to 40.0 27 - Sound Ctrl IGV1 Open Deg 10 40
11 gv1_dmin 0.0 to 10.0 2 - IGV1 Minimum Open Deg 0 10
12 gv1_dmax 90 to 120.0 109 - IGV1 Maximum Open Deg 90 120
13 gv1_pmin 0.0 to 100.0 5 % IGV1 Minimum Position 0 100
14 gv1_pful 0.0 to 100.0 100 % IGV1 Full Load Position 0 100
15 sgl_o 1.0 to 3.0 2 ^F Surge Line Oset 1 3
16 sgl_lo 0.5 to 3.0 1.5 ^F Surge Line Lower DB 0.5 3
17 sgl_ho 0.1 to 3.0 1.5 ^F Surge Line Upper DB 0.1 3
18 sgl_shfh -1.000 to 0.000 -0.01 - Surge Line Shape Factor -1 0
19 sgl_sh 0.000 to 1.000 0.01 - Sound Line Shape Factor 0 1
20 sgl_spdf 0.00 to 3.00 2 - Surge Line Speed Factor 0 3
21 surg_del 0 to 120 15 sec Surge Delay Time 0 120
22 surge_t 7 to 10 8 min Surge Time Period 7 10
23 surge_a 5.0 to 40.0 20 % Surge Delta Amps % 5 40
24 gvstp_sg 1.0 to 3.0 2 % GV1 Close Step Surge 1 3
25 vfdstpsg 1.0 to 5.0 1.5 % VFD Speed Step Surge 1 5
26 hgbpstsg 1.0 to 10.0 4 % EC Valve Step Surge 1 10
27 sgl_pro 0.00 to 5.0 0 ^F Surge Prole Oset 0 5
28 high_e 0 to 1 1 - High Eciency Mode 0 1
29 noi_alt 0 to 1 0 - High Noise Alert 0 1
CFGLIMIT 13H 8 //MAINMENU/CONFIG
1 evap_al 0.5 to 15.0 5 ^F Evap Approach Alert 0.5 15
2 cond_al 0.5 to 15.0 6 ^F Cond Approach Alert 0.5 15
3 cpov_lo 90.0 to 157.0 140 PSIG Cond Press Override Low 90 157
4 cpov_hi 200.0 to 265.0 250 PSIG Cond Press Override High 200 265
5 cpcut_lo 160.0 to 165.0 160 PSIG Cond Press Cutout Low 160 165
6 cpcut_hi 270.0 to 275.0 275 PSIG Cond Press Cutout High 270 275
7 ert_ovdt 2 to 5 3 ^F Evap Override Delta T 2 5
8 ert_trip 0 to 40 33 °F Evap Refrig Trippoint 0 40
9 ep_ov 90 to 157 140 PSIG High Evap Press Override 90 157
10 ep_cut 160 to 170 165 PSIG High Evap Press Cutout 160 170
11 cdfreeze -20.0 to 35.0 34 °F Condenser Freeze Point -20 35
12 dgt_alrt 125 to 200 200 °F Comp Discharge Alert 125 200
13 mt_over 150 to 200 200 °F Comp Motor Temp Override 150 200
14 tb_alert 155 to 175 175 °F Comp Bearing Temp Alert 155 175
15 tb_trip 175 to 185 185 °F Comp Bearing Temp Trip 175 185
16 tb_alt2 185.0 to 210.0 210 °F Comp Bearing Alert R6&7 185 210
17 tb_trip2 210.0 to 220.0 220 °F Comp Bearing Trip R6&7 210 220
18 bri_min 10.0 to 34.0 34 °F Minimum Brine LWT 10 34
19 lwtp_sp 41.0 to 50.0 42.8 °F Heating LWT Protect Set 41 50
20 evap_cut 0.5 to 50 5 PSI Evap Flow Delta P Cutout 0.5 50
21 cond_cut 0.5 to 50 5 PSI Cond Flow Delta P Cutout 0.5 50
22 cond_val 0.5 to 50 50 PSI Cond Hi Flow DP Limit 0.5 50
23 cond_alm 0 to 1 0 - Cond Hi Flow Alarm 0 1
24 cpov_dl 18 to 35.6 20 PSIG Cond Pre Override DV 44* 18 35.6
25 cpcut_dl 30to 38 30 PSIG Cond Pre Cutout DV 44** 30 38
26 cpov_dh 20 to 56 55 PSIG Cond Pre Override DV 72 20 56
27 cpcut_dh 59 to 60.3 59 PSIG Cond Pre Cutout DV 72 59 60.3
28 tb_alt3 90.0 to 120. 104 °F Comp Bearing Alert DV 90 120
29 tb_trip3 121.0 to 150.0 122 °F Comp Bearing Trip DV 121 150
30 lwtp_sp 41.0 to 50.0 42.8 °F Heating LWT Protect Set 41 50
31 ep_ovdv 20 to 56 55 PSIG Hi Evap Pre Override DV 20 56
32 ep_cutdv 59 to 60.3 59 PSIG Hi Evap Pre Cutout DV 59 60.3
* NOTE: this value must be setted by service personnel according to the actual pressure switch jump value
* * NOTE: this value must be setted by service personnel according to the actual pressure switch priority controlled value, and the given value should be less than the value
of * - 2.4 F.