EasyManua.ls Logo

Carrier PIC 5+ - Check Relief Devices; Inspect Wiring

Carrier PIC 5+
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
   
CONF_OPT 13H 10 //MAINMENU/CONFIG
       
1 astart 0 to 1 0 - Auto Restart Option 0 1
2 commsens 0 to 1 0 - Common Sensor Option 0 1
3 hgbp_opt 0 to 3 0 - EC Valve Option 0 3
4 - No=0, Cont.=1,
5 - ON/OFF=2, mA=3
6 hgbp_sel 0 to 3 0 - EC Valve Selection 0 3
7 - Disable=0, Surge=1
8 - Low Load=2, Comb=3
9 hpop_gv1 0.5 to 10.0 5 % ECV Open IGV1 Position 0.5 10
10 hgcl_gv1 1.5 to 20.0 10 % ECV Close IGV1 Position 1.5 20
11 hgb_to 0.5 to 10 4 ^F ECV O DT for Low Load 0.5 10
12 hgb_ton 0.5 to 10 2 ^F ECV On DT for Low Load 0.5 10
13 hgbp_ldb 0.5 to 2.0 1 ^F ECV Low Load DB 0.5 2
14 hdpv_opt 0 to 1 0 - Head Pres Valve Option 0 1
15 hdp_0 20 to 85 25 PSI Head Pres Delta P 0% 20 85
16 hdp_100 20 to 85 50 PSI Head Pres Delta P 100% 20 85
17 hdpv_min 0 to 100 0 % Head Pressure Min Output 0 100
18 ice_opt 0 to 1 0 - Ice Build Option 0 1
19 ice_recy 0 to 1 0 - Ice Build Recycle 0 1
20 ice_term 0 to 2 0 - Ice Build Termin Source 0 2
21 - Temp=0,Contact=1,Both=2
22 tfh_sp 55 to 105 75 °F Tower Fan High Setpoint 55 105
23 leak_en 0 to 1 0 - Refrig Leakage Option 0 1
24 leak_ma 4 to 20 20 mA Refrig Leakage Alarm mA 4 20
25 exv_opt 0 to 1 0 - Oil EXV Option 0 1
26 oil_high 100 to 140 122 °F Oil Temp High Threshold 100 140
27 oil_low 90 to 130 113 °F Oil Temp Low Threshold 90 130
28 gt_fact 0.25 to 3.00 1 - Gas Torque Factor 0.25 3
29 gv_srd_f 0.70 to 1.20 0.95 - Guide Vane/SRD Factor 0.7 1.2
30 pd_tcfg 0 to 60 15 min Power Recovery Timeout 0 60
31 evap_t_o 0 to 1 1 - Evap Liquid Temp Opt 0 1
32 evap_ref 0 to 1 1 - Evap App Calc Selection 0 1
33 - Sat Temp=0, Ref Temp=1
34 cfa_opt 0 to 1 0 - Condenser Flush Alert 0 1
35 cusa_opt 0 to 1 0 - Customer Alert Option 0 1
36 wp_opt 0 to 2 0 - Water Pressure Option 0 2
37 - No=0, Pres.=1, Pres.D=2
38 wfm_opt 0 Water Flow Measurement 0 3
39 - No=0, Flow Meter=1,
40 - Water Pres. D=2
41 fs_opt 0 to 1 0 - Water Flow Determination 0 1
42 - Sat Temp=0,Flow Switch=1
43 ow4ma 0 to 200 0 GPS
Water Flow at 4mA 0 200
44 ow20ma 0 to 200 0 GPS Water Flow at 20mA 0 200
45 chwf_bas 0 to 150 0 GPS Evap Flow Rate Baseline 0 150
46 evpd_bas 0 to 20 0 PSI Evap Pres Drop Baseline 0 20
47 cdwf_bas 0 to 150 0 GPS Cond Flow Rate Baseline 0 150
48 cdpd_bas 0 to 20 0 PSI Cond Pres Drop Baseline 0 20
49 wpd_20ma 10 to 40 10 PSI Water Pres Drop @20mA 10 40
50 vssv_dly 0 to 10 5 min Vapor Source SV Delay 0 10
51 opvfdmax 35 to 60 50 PSI Max Oil Pressure Di 35 60
52 opvfdstp 0 to 10 7 % Oil Pump VFD Max Step 0 10
53 0 to 1 0 - Vapor Source SV Option 0 1
54 pgon_opt 0 - Purge On Idle Option 0 1
   
CONF_IOB 13H 11 //MAINMENU/CONFIG
       
1 lv_enth 17.0 to 19.0 17 Volts Low Entered Volt V1 IOB 17 19
2 lv_exth 19.0 to 21.0 19 Volts Low Exited Volt V2 IOB 19 21
3 typ_ai11 0 to 6 4 - 1 IOB1 AI#1 Type 0 6
4 typ_ai12 0 to 6 4 - IOB1 AI#2 Type 0 6
5 typ_ai13 0 to 6 4 - IOB1 AI#3 Type 0 6
6 typ_ai14 0 to 6 4 - IOB1 AI#4 Type 0 6
7 typ_ai19 0 to 5 2 - IOB1 AI#9 Type 0 5

Table of Contents

Other manuals for Carrier PIC 5+