If compressor runs, pump down the unit. (Refer to
sor pressure to a recovery
Remove bolts from suction and discha
transducer (SPT), the wiring to the high pressure
switch (HP) and low pressure (BP) as necessary.
outlined when removing the compressor.
The service replacement compressor is sold without
retain the original capacity control valves for use on
replacement compressor. Check oil level in service
replacement compressor. (Refer to sections 2.3, and
pump) to the suction and discharge service valves.
(29.90” Hg vacuum = 75.9 cm Hg vacuum). Turn off
valves on both lines to pump.
eat (open) both suction and dischar
It is important to check the compressor oil leve
new compressor and fill if necessary.
r oil level. (Refer to sectio
o check oil level in 05K com
ensure that no foaming of the oil is present after 20
after 20 minutes of operation, check the refrigerant
system for flood-back of liquid refrigerant. Correct
this situation before performing step 3.