The valve is controlled by the micro (P2).The valve
opens and closes at the values chosen by FN6.
See Table 1--4 “Bypass Valve Setup”.
suction pressure is below the value chosen by FN6
(default = 1.17 bars). If the pressure rises above the
value chosen by FN6 (default = 1.72 bars) the valve is
Run relay is energized via W1 output.
Diesel/Electric relay is energized via N2 output :
tion. Fuel pump is energized.
and subsequent motor start is prevented.
T2 output. Engine will crank for 10 seconds or until
sensed on. If engine does not start a 15 seconds null
period will elapse before next start attempt. Run relay
DER relay is energized via N2 output.
RR is energized. Electrical power is supplied to the
standby motor for starting.