VVT Zone Controller 61
Point Name/Description
Default/Range
Min Setpoint Separation
Minimum separation that must be maintained between the
heating and cooling setpoints.
D:
R:
4°F
2 to 10°F
Occ Override Normal Logic State
The normal state of the controller's
Remote
Occupancy
input. If the input's contact is the same state as the configured state, the
controller follows its controlling schedule. If the contact is in the opposite state of the
configured state, the controller is forced into the unoccupied mode.
D:
R:
Open
Open/Closed
RH Sensor Min Input Volts
The lowest voltage that should be read from the relative
humidity (RH) sensor.
D:
R:
0.00 V
0 to 5.00 V
RH Sensor Max Input Volts
The highest voltage that should be read from the RH sensor. D:
R:
5.00 V
0 to 5.00 V
RH Sensor Value @ Min Volts
The % relative humidity that correlates to the RH sensor's
low voltage reading.
D:
R:
0%
0 to 99%
RH Sensor Value @ Max Volts
The % relative humidity that correlates to the RH sensor's
high voltage reading.
D:
R:
100%
0 to 100%
CO2 Sensor Min Input Volts
The lowest voltage that should be read from the CO
2
D:
sensor.
R:
1.00 V
0 to 5.00 V
CO2 Sensor Max Input Volts
The highest voltage that should be read from the CO
2
D:
sensor.
R:
5.00 V
0 to 5.00 V
CO2 Sensor Value @ Min Volts
The ppm value that correlates to the CO
2
D:
sensor's low
voltage reading.
R:
0ppm
0 to 9999 ppm
CO2 Sensor Value @ Max Volts
The ppm value that correlates to the CO
2
D:
sensor's high
voltage reading.
R:
2000 ppm
0 to 9999 ppm
PD (Pressure Dependent) Control :
Damper Motor Travel Time
The actuator's travel time from full closed to full open.
This field is fixed at 205 seconds.
D: 205 seconds
Direction Clockwise
If
Damper Actuator
is set to
Built-in actuator
, set this field to
the damper's position when it rotates clockwise.
D:
R:
Closed
Open/Closed
Target Damper Position
- The current damper position. To override normal control for
troubleshooting purposes, select
Lock value to
and then enter a value. The damper
moves to that position until
Lock value to
checkbox is cleared.
R: 0 to 100%
Auxheat
- The current configured
Reheat Min Damper Position
. To override normal
control for reheat troubleshooting purposes, select
Lock value to
and then enter a
value. The damper moves to that position until
Lock value to
checkbox is cleared.
R: 0 to 100%
Fan
The current value of the fan output relay. To override normal control for
troubleshooting purposes, select
Lock value to
and then enter
On
or
Off
. The relay
stays in that state until the
Lock value to
checkbox is cleared.
R: On/Off
Cooling Min Damper Position
The minimum damper position the terminal controls
to when the air source mode is Cooling, Vent, or Free Cooling and the space
requirements for cooling are at a minimum. We recommend that you set this no lower
than 10%.
D:
R:
20%
0 to 100%