Appendix A: VVT Zone Controller Points/Properties
62 VVT Zone Controller
Point Name/Description
Default/Range
Cooling Max Damper Position
The maximum damper position the terminal controls
to when the air source mode is Cooling, Vent, or Free Cooling and the space
requirements for cooling are at a maximum.
D:
R:
100%
0 to 100%
Reheat Min Damper Position
For Single Duct units with ducted reheat. Set to the
desired damper position at which the reheat will provide optimum performance. This
value is compared to the
Cooling Min Damper Position
value, and the greater of the
two values determines the damper position.
D:
R:
45%
0 to 100%
Heating Min Damper Position
The minimum damper position the terminal controls
to when the air source mode is Heat and the space requirements are at a minimum.
D:
R:
20%
0 to 100%
Heating Max Damper Position
The maximum damper position the terminal controls
to when the air source mode is Heat and the space requirements are at a maximum.
D:
R:
20%
0 to 100%
Vent Position
The ventilation damper position the terminal controls to when the air
source mode is Vent and the terminal mode is not in the Heat or Cool mode. If
Linkage is not active, the zone determines vent mode by verifying that its SAT sensor
is between 65°F and 80°F.
D:
R:
50%
0 to 100%
Test and Balance
Use the following command buttons when commissioning a zone, balancing the system 36 (page ),
replacing the zone controller, or troubleshooting. If
Automatic Control
Calibrated Damper Close
Forces the damper closed so the 0% damper position can be set.
is not selected within 4 hours, the controller will
resume normal control.
Calibrated Damper Open
Forces the damper to its maximum open position so that the 100% damper position can be
set.
Cool Max
Forces the damper to its cool maximum position regardless of its current local mode.
Cool Min
Forces the damper to its cool minimum position regardless of its current local mode.
Automatic Control
Returns the damper to its normal control routines.
This must be activated when you finish using
any of the other Test and Balance commands.
Damper Full Close
Overrides the damper to its full closed position.
Heat Max
Forces the damper to its heat maximum position regardless of its current local mode.
Heat Min
Forces the damper to its heat minimum position regardless of its current local mode.
Reheat Min
Forces the damper to its reheat position regardless of its current local position.
Vent
Forces the damper to its ventilation position regardless of its current local mode.
System Space Temperature
The current value of the controlling space temperature
received over the network from another source. -999 indicates no value has been
received and it will not be used.
R: -50 to 150°F
System Space RH
The relative humidity received over the network. -999 indicates no
value has been received and it will not be used.
R: 2 to 100%
System Space AQ
The indoor air quality received over the network. -999 indicates no
value has been received and it will not be used.
R: 300 to 9999 ppm
System Cool Demand Level
This value received over the network and used by the
demand limiting function to expand the cooling setpoint.
R: 0 to 3
System Heat Demand Level
This value received over the network and used by the
demand limiting function to expand the heating setpoint.
R: 0 to 3
System Outdoor Air Temperature
The OAT received over the network. R: -50 to 150°F