APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
COOL COOLING CONFIGURATION
Z.GN
Capacity Threshold Adjst -10 to 10 Z_GAIN 1 35,42-44
MC.LO
Compressor Lockout Temp -20 to 55 dF OATLCOMP 4 35,45
C.FOD
Fan-off Delay, Mech Cool 0 to 600 sec COOL_FOD 60 35,35
MLV
Min. Load Valve ? (HGBP) Yes/No MLV_SEL No 35,35
DS.EN
Enable Digital Scroll? Yes/No DIGCMPEN No 35,36
DS.MC
DS Min Digital Capacity 25 to 100 % MINCAPDS 50 35,36
DS.AP
Dig Scroll Adjust Delta 0 to 100 % DSADJPCT 100 35,36
DS.AD
Dig Scroll Adjust Delay 15 to 60 sec DSADJDLY 20 35,36
DS.RP
Dig Scroll Reduce Delta 0 to 100 % DSREDPCT 6 35,36
DS.RD
Dig Scroll Reduce Delay 15 to 60 sec DSREDDLY 30 35,36
DS.RO
Dig Scroll Reduction OAT 70 to 120 dF DSREDOAT 95 35,36
DS.MO
Dig Scroll Max Only OAT 70 to 120 dF DSMAXOAT 105 35,36
HPSP
Head Pressure Setpoint 80 to 150 dF HPSP 110 35,36
LASP
Low Ambient Setpoint 70 to 150 dF LASP 100 35
M.M.
Motor Master Control ? Yes/No MOTRMAST No
35
MM.OF
Motor Master Setpoint Offset 20 to 20 dF MMSPOFST –10
35
MM.RR
Motor Master PD Run Rate 10 to 120 sec MM_RATE 10
35
MM.PG
Motor Master Proportional Gain 0.0 to 5 MM_PG 1
35
MM.DG
Motor Master Derivative Gain 0 to 5 MM_DG 0.3
35
MM.TI
Motor Master Integration Time 0 to 50 MM_TI 30
35
A1.EN
Enable Compressor A1 Enable/Disable CMPA1ENA Enable 35,36
A2.EN
Enable Compressor A2 Enable/Disable CMPA2ENA Enable 35,36
B1.EN
Enable Compressor B1 Enable/Disable CMPB1ENA Enable 35,36
B2.EN
Enable Compressor B2 Enable/Disable CMPB2ENA Enable 35,36
CS.A1
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable 35,36,110
CS.A2
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable 35,36,110
CS.B1
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable 35,36,110
CS.B2
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable 35,36,110
REV.R
Rev. Rotation Verified ? Yes/No REVR_VER No 35,36,106
H.SST
Hi SST Alert Delay Time 5 to 30 min HSSTTIME 10 35,37,106
OV.DB
Outdoor VFD SCT DeadBand 0 to 20 dF OV_SCTDB 2 35
OV.RH
Outdoor VFD Dehum-RH SPD 0 to 100 % OV_RH 50 35
LA.ST
OV MinStartSpeed Low Amb 0 to 100 % OV_STMIN 12 35
OV.EN
Outdoor VFD Enable
No/Yes OV_ENA No 35
ODV.A
OUTDOOR VFD-A CONFIGS
35
N.VLT
OV-A Nominal Motor Volts
0 to 999 v OVA_NVLT 35
N.AMP
OV-A Nominal Motor Amps
0 to 999 A OVA_NAMP 35
N.FRQ
OV-A Nominal Motor Freq
10 to 500 Hz OVA_NFRQ 60 35
N.RPM
OV-A Nominal Motor RPM
50 to 30000 rpm OVA_NRPM 850 35
N.PWR
OV-A Nominal Motor HPwr
0 to 500 hp OVA_NPWR 35
M.DIR
OV-A Motor Direction
0=FORWARD, 1=REVERSE 0 OVA_MDIR 0 35
ACCL
OV-A Acceleration Time
0 to 1800 s OVA_ACCL 30 35
DECL
OV-A Deceleration Time
0 to 1800 s OVA_DECL 30 35
SW.FQ
OV-A Switching Frequency
0 to 3 OVA_SWFQ 1 35
ODV.B
OUTDOOR VFD-B CONFIGS
35
N.VLT
OV-B Nominal Motor Volts
0 to 999 v OVB_NVLT 35
N.AMP
OV-B Nominal Motor Amps
0 to 999 A OVB_NAMP 35
N.FRQ
OV-B Nominal Motor Freq
10 to 500 Hz HOVB_NFRQ 60 35
N.RPM
OV-B Nominal Motor RPM
50 to 30000 rpm rpOVB_NRPM 850 35
N.PWR
OV-B Nominal Motor HPwr
0 to 500 hp hOVB_NPWR 35
M.DIR
OV-B Motor Direction
0=FORWARD, 1=REVERSE 0 OVB_MDIR 0 35
ACCL
OV-B Acceleration Time
0 to 1800 s OVB_ACCL 30 35
DECL
OV-B Deceleration Time
0 to 1800 s OVB_DECL 30 35
SW.FQ
OV-B Switching Frequency
0 to 3 OVB_SWFQ 1 35
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF
EDT Reset Configuration 0 to 3 (multi-text strings) EDRSTCFG 0 21,34,34
RTIO
Reset Ratio 0 to 10 RTIO 2 21,34
LIMT
Reset Limit 0 to 20 ^F LIMT 10 21,34
RES.S
EDT 4-20 ma Reset Input Enable/Disable EDTRSENS Disable 21,31,34,105