APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
O.PID OUTDOOR VFD PID CONFIGS
OV.RR
Outdoor VFD PI Run Rate 5 to 120 OV_RATE
OV.PG
Outdoor VFD Prop. Gain 0 to 5 OV_PG
OV.TI
Outdoor VFD Integ. Time 0.5 to 200 OV_TI
OV.AU
Outdoor VFD Anti-Windup 0.1 to 1 OV_AU
LA.PG
OV Prop. Gain at Low Amb 0 to 5 OV_PG_LA
LA.TI
OV Intg. Time at Low Amb 0.5 to 200 OV_TI_LA
HEAT HEATING CONFIGURATION
HT.CF
Heating Control Type 0 to 4 HEATTYPE 0 51,52,56,74
HT.SP
Heating Supply Air Setpt 80 to 120 dF SASPHEAT 85 51
OC.EN
Occupied Heating Enabled Yes/No HTOCCENA No 51
LAT.M
MBB Sensor Heat Relocate Yes/No HTLATMON No 51
G.FOD
Fan-Off Delay, Gas Heat 45 to 600 GAS_FOD 45 51
E.FOD
Fan-Off Delay, Elec Heat 10 to 600 HEAT_FOD 30 51
SG.CF
STAGED GAS CONFIGS 51
HT.ST
Staged Gas Heat Type 0 to 4 HTSTGTYP 0 51,53,54
CAP.M
Max Cap Change per Cycle 5 to 45 HTCAPMAX 45 51,53,53
M.R.DB
S.Gas DB min.dF/PID Rate 0 to 5 HT_MR_DB 0.5 51,53,53
S.G.DB
St.Gas Temp. Dead Band 0 to 5 ^F HT_SG_DB 2 51,53,53
RISE
Heat Rise dF/sec Clamp 0.05 to 0.2 HTSGRISE 0.06 51,53
LAT.L
LAT Limit Config 0 to 20 ^F HTLATLIM 10 51,53
LIM.M
Limit Switch Monitoring? Yes/No HTLIMMON No 51,53
SW.H.T
Limit Switch High Temp 110 to 180 dF HT_LIMHI 170 51,53
SW.L.T
Limit Switch Low Temp 100 to 170 dF HT_LIMLO 160 51,53
HT.P
Heat Control Prop. Gain 0 to 1.5 HT_PGAIN 1 51,53
HT.D
Heat Control Derv. Gain 0 to 1.5 HT_DGAIN 1 51,53
HT.TM
Heat PID Rate Config 60 to 300 sec HTSGPIDR 90 51,53
SP SUPPLY STATIC PRESS.CFG.
SP.CF
Static Pressure Config
0 to 1 (multi-text strings) STATICFG No 25,57,60
CV.FD
Constant Vol IDF is VFD?
Yes/No CVIDFVFD No 57,58
SP.FN
Static Pres.Fan Control?
Yes STATPFAN Yes 57,58
SP.S
Static Pressure Sensor
Enable/Disable SPSENS Disable 57,58
SP.LO
Static Press. Low Range
–10 to 0 SP_LOW 0 57,58
SP.HI
Static Press. High Range
0 to 10 SP_HIGH 5 57,58
SP.SP
Static Pressure Setpoint
0 to 5 " H2O SPSP 1.5 57,58
SP.MN
VFD Minimum Speed
0 to 100 % STATPMIN 20 25,57,58
SP.MX
VFD Maximum Speed
0 to 100 % STATPMAX 100 25,57,58
SP.FS
VFD Fire Speed Override
0 to 100 % STATPFSO 100 57,58,65
HT.V.M
VFD Heating Min Speed
75 to 100 % VFDHTMIN 75
57,58
SP.RS
Stat. Pres. Reset Config
0 to 4 (multi-text strings) SPRSTCFG 0
25,57,58
SP.RT
SP Reset Ratio (/dF)
0 to 2.00 SPRRATIO 0.2
57,58
SP.LM
SP Reset Limit in iwc()
0 to 2.00 SPRLIMIT 0.75
57,58
SP.EC
SP Reset Econo.Position
0 to 100 % ECONOSPR 5
57,58
S.PID
STAT.PRESS.PID CONFIGS
57,59
SP.TM
Stat.Pres.PID Run Rate 1 to 200 sec SPIDRATE 2 57,59
SP.P
Static Press. Prop. Gain 0 to 100 STATP_PG 20 57,59
SP.I
Static Pressure Intg. Gain 0 to 50 STATP_IG 2 57,59
SP.D
Static Pressure Derv. Gain 0 to 50 STATP_DG 0 57,59
SP.SG
Static Press.System Gain 0 to 50 STATP_SG 1 57,59