LIST OF USABLE REGISTERS
The MODBUS-RTU protocol implemented on this instrument can manage a maximum of
32 registers read and written in a single query or response.
R = the register can be read only
W = the register can be written only
R/W = the register can be both read and written
H = high half of the DOUBLE WORD forming the number
L = low half of the DOUBLE WORD forming the number
REGISTER DESCRIPTION
Saving to
EEPROM
ACCESS
40002
Type of instrument
- R
40008
GROSS WEIGHT H
- R
40009
GROSS WEIGHT L
- R
40010
NET WEIGHT H
- R
40011
NET WEIGHT L
- R
40014
Raw AD Data_H
- R
40015
Raw AD Data_L
- R
40017
Set point 1 H
Y R/W
40018
Set point 1 L
Y R/W
40019
Set point 2 H
Y R/W
40020
Set point 2 L
Y R/W
40021
Set point 3 H
Y R/W
40022
Set point 3 L
Y R/W
40023
Set point 4 H
Y R/W
40024
Set point 4 L
Y R/W
40025
Set point 5 H
Y R/W
40026
Set point 5 L
Y R/W
83