- 18 -
16. Technical specification for BB2 control box
Manufacturer Cerlic Controls AB, Solna, Sweden
Name BB2
Measurement See drawing in section 17
Enclosure NEMA4 (IP65)
Weight 2.8 lbs (1,3 kg)
Supply voltage 85 – 250 V AC, 50 – 60 Hz
Fuse 3.15 A Slow 250V 4 x 20mm
Power Usage 20 Watts (0.180 Amps @ 110V)
Ambient temp
-4 – +122 °F (-20 – +50 °C)
Internal Heating
Full power below 63 °F (17 °C), Off above 66 °F (19 °C)
Storage temp
32 - +140°F (0 – 60 °C)
Connected
sensors
Displayed on the screen at start-up
Output signals Two (2 ) 4 – 20 mA (20 – 4 mA), galvanic isolated, 500 ohm
Relays Selectable function, 85-250VAC max 30VA, 24VDC max 100mA or
Dry contacts 250VAC / 30VDC, max 30 VA, normally open
OPTIONAL PARTS FOR BB2 CONTROL BOX:
Aluminum handrail mounting plate predrilled for BB2 P/N 10605533
or solenoid valves w/ u-bolts, outside US version
Aluminum handrail mounting plate predrilled for BB2 P/N 31204049
or solenoid valves w/ u-bolts, US version
33 ft. (10m) cable for. Connection cable with plug-in. P/N 20805510
Y-Splitter for two sensors to one BB2 control box P/N 21505534
Solenoid valve for flushing P/N 11705516