EasyManua.ls Logo

Chroma 3302 - Handler Interface (Option); General

Default Icon
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Handler Interface (Option)
7-1
7. Handler Interface (Option)
7.1 General
If you have the HANDLER INTERFACE option, connect from the HANDLER INTERFACE
on the rear panel to a handler. Connect the control lines to the handler. See Table 7-1. As
indicated in the specifications at the front of this manual. The output signal come from
open-collector drivers that pull each signal line to a low voltage when that signal is active and
let it float when inactive. Each external circuit must be powered by a positive voltage, up to
30V(max), with sufficient impedance (pull-up resistors) to limit the active-signal (logic-low)
current to 16mA(max).
Caution :
Each relay or other inductive load requires a CLAMPING DIODE (rectifier) across it
(cathode connected to the power-supply end of the load) typically.
Table 7-1 Handler Interface Key
Signal Name Pin No. Function (All signal
active low
)
START 25 Initiates measurement (External Trigger).
EOM 8
End of measurement
judgment signals are valid.
ACQ over 27 "Data acquisition over"
DUT removal OK
BIN 0 19 Q
D
R
¦Z¦ No-Good
BIN 1 2 L
C
R
¦Z¦ Good
BIN 2 20 L
C
R
¦Z¦ Good
BIN 3 3 L
C
R
¦Z¦ Good
BIN 4 21 L
C
R
¦Z¦ Good
BIN 5 4 L
C
R
¦Z¦ Good
BIN 6 22 L
C
R
¦Z¦ Good
BIN 7 5 L
C
R
¦Z¦ Good
BIN 8 23 L
C
R
¦Z¦ Good
BIN 9 6 L
C
R
¦Z¦ No-Good
1,7 Ground connection
9 DC bus(
5V) available
commonly for opto-couplers.
Limit the load to 25mA(max.).
The input signal is also active low and also requires a positive-voltage external circuit,
which must pull the signal line down below 0.4V, but not less than 0V, i.e., not negative.
The logic-low current is 0.4mA (max.). For the inactive state (logic high) the external
circuit must pull the signal line above +2.5V, but no above +5V.

Table of Contents

Related product manuals