MAINTENANCE WITH Q & A
70
GENERAL TROUBLESHOOTING PROCEDURES
R-508B/R-23
head pressure
too low
R-404A head
pressure too
high
Maximum condenser inlet air = 80°F
Restricted air cooled condenser
Recover, evacuate and recharge
R-404A head
pressure too
low
Location may need to be changed
Insufficient compressor oil
Consult Cincinnati Sub Zero
Bend tubes away from contact
Compressor mounting loose
Table 5-4: General Troubleshooting Procedures (Continued)
HUMIDITY TROUBLESHOOTING PROCEDURES (OPTIONAL ATOMIZER)
reaching desired
level
*Applies only to
units with an
atomizing
humidity system.
Check heater and replace as required
*Atomizing nozzle clogged
Remove and clean. Replace demineralizer
filter if necessary
Water is not connected to unit
Water control solenoid not energized
Check coil - replace if burned
Dispersion tube is clogged
Chamber fan not functioning
Check fan circuit check fan blade for
tightness on shaft
Demineralizer cartridge clogged internally
Solid state sensor defective
*Water metering valve not adjusting
properly
Adjust to 20.25 cubic centimeters
Defective heating element
See corresponding manufacturers manual
in the Accessories folder for information
Table 5-5: Humidity System Troubleshooting Procedures