or SEL.
5�1�3�-POSITIVE SECURITY SETTING OF THE MAIN RELAY
“Std”, contacts are on standby, terminals 14 - 15 (NC) and 13 - 15 (NO).
 “+”, contacts change status on powering the device, the + sign is displayed. Terminals 14 -15 
(NO) and 13 -15 (NC).
Figure 24: Positive security setting� 
5�1�4�- SETTING THE PRE-ALARM RELAY
The PROG/PAG  key control the pre-alarm relay and main relay settings using SETUP.
If the button is pressed for a short time the pre-alarm setting is entered. “Alarm” appears on the  
display. Also the pre-alarm threshold appears as a % of the sensitivity setting and the pre-alarm 
delay. To exit press PROG.
Figure 25: Setting the pre-alarm relay� 
5�1�4�1�- Setting of the pre-alarm current
This is in terms of the program value in the main relay. Pressing Id enters to change the value.
Relative values are shown as a % of the preset trip current.  Pressing Id changes the values: 
OFF, 50, 60,  70,  80 and MAIN�
Where: 
  OFF: pre-alarm disabled
  MAIN: the pre-alarm continues to trip the main channel.
Figure 26: Setting of the pre-alarm current�