Problem
Unable to lock the configuration. The following syslog message is displayed:
<Tue Apr 30 10:02:47 2019> ERROR!!! Failed to lock config, aborting migration
...
Action to be performed
Use the migrate sup kickstart <sup3-kickstart-image> system <sup3-system-image> command again.
Problem
In case auto-boot is not disabled before the insertion of the supervisor-3E module, the following syslog
message is displayed:
<Tue Apr 30 10:02:47 2019> ERROR!!! Standby Supervisor config failed,
aborting migration ...
Action to be performed
Use the migrate sup kickstart <sup3-kickstart-image> system <sup3-system-image> command again.
Problem
After powering down the supervisor-2E module, the switch will check for the presence of a module in
the slot from which the supervisor-2E module was removed. This check happens every 30 minutes after
the supervisor-2E module has been removed. In case this check to detect the presence of the supervisor
module fails, the following syslog message is displayed:
<Tue Apr 30 10:02:47 2019> ERROR!!! Module information retrieve failed
Action to be performed
None. There is no impact on the migration process.
Problem
A supervisor-2E module in inserted instead of a supervisor-3E module. The following syslog message
is displayed:
<Tue Apr 30 10:02:47 2019> ERROR!!! Supervisor-2 (N77-SUP2E) is inserted in slot
<slot_number> instead of Supervisor-3 (N77-SUP3E), aborting migration ...
Action to be performed
Ensure that the newly inserted supervisor module is the supervisor-3E module.
Problem
In case the supervisor-3E module is not inserted into the standby slot within 30 minutes after the supervisor
2E module has been powered down, the following syslog message is displayed:
<Tue Apr 30 10:02:47 2019> ERROR!!! Timeout waiting for Supervisor-3 (N77-SUP3E)
to be inserted in slot <slot_number>, aborting migration ...
Action to be performed
Use the migrate sup kickstart <sup3-kickstart-image> system <sup3-system-image> command again
and ensure that the supervisor 3E module is inserted into the standby slot within 30 minutes after the
supervisor 2E module has been powered down.
Problem
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
OL-30452-01.110
Installing or Replacing Modules, Fan Trays, and Power Supplies
Troubleshooting