Full Redundancy
Mode
Input Source
Redundancy
Mode
Power Supply
Redundancy
Mode
Combined ModePower SuppliesPower Inputs
—
——3100 W11 input (210 V)
3100 W3100 W3100 W6200 W2
3100 W3100 W6200 W9300 W3
6200 W6200 W9300 W12,400 W4
6200 W6200 W12,400 W15,500 W5
9300 W9300 W15,500 W18,600 W6
9300 W9300 W18,600 W21,700 W7
12,400 W12,400 W21,700 W24,800 W8
A combination of 3-kW DC and 3.5-kW HVAC/HVDC power supplies can be used.
Note
Weights and Quantities for the Chassis, Modules, Fan Trays,
and Power Supplies
QuantityWeight per UnitComponent
1160.0 lb (72.6
kg)
Cisco Nexus 7710 Chassis (N77-C7710)
1 or 28.5 lb (3.9 kg)Supervisor module (N77-SUP2E)
1 or 27.7 lb (3.5 kg)Supervisor module (N77-SUP3E)
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
OL-30452-01.146
Switch Specifications