Maximum Power Available for 3.5-kW Inputs (DC)
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3.5-kW HVAC/HVDC power supplies depending on DC power
inputs, numbers of power supplies, and the mode used.
Full Redundancy
Mode
Input Source
Redundancy
Mode
Power Supply
Redundancy
Mode
Combined ModePower SuppliesPower Inputs
———3500 W11 input (380 V)
3500 W3500 W3500 W7000 W2
3500 W3500 W7000 W10,500 W3
7000 W7000 W10,500 W14,000 W4
7000 W7000 W14,000 W17,500 W5
10,500 W10,500 W17,500 W21,000 W6
10,500 W10,500 W21,000 W24,500 W7
14,000 W14,000 W24,500 W28,000 W8
—
——3500 W11 input (220/240
V)
3500 W3500 W3500 W7000 W2
3500 W3500 W7000 W10,500 W3
7000 W7000 W10,500 W14,000 W4
7000 W7000 W14,000 W17,500 W5
10,500 W10,500 W17,500 W21,000 W6
10,500 W10,500 W21,000 W24,500 W7
14,000 W14,000 W24,500 W28,000 W8