SpecificationDescription
2790 VA @ 200 VACMaximum Input VA
2500 W @ 200 to 240 VAC
1300 W @ 100 to 120 VAC
Maximum output power per power supply
35 A (sub cycle duration)Maximum inrush current
8530 BTUMaximum Heat Output
12 ms @ 2500 WMaximum hold up time
12 VDC @ 208 APower supply output voltage
3.3 VDC @ 5APower supply standby voltage
Climate Savers PlatinumEfficiency Rating
10% 20% 50% 100%
93.5% 94.9 % 95% 93%
Efficiency (80 Plus Platinum Certified)
IEC320 C20Input connector
DC wiring must meet your local codes and regulations, we recommend using a licensed local electrician to
install the DC wiring needed.
To determine the number of power supply units needed for the blade server, remember that each single slot
server is budgeted a max 550 W and each full width server is budgeted a max 1100 W. For a more detailed
estimate, contact Cisco Sales.
For information about supported power cords, see the Cisco UCS 5108 Server Chassis Installation Guide.
Supported AC Power Cords and Plugs
The AC power connectors on the blade server chassis PDU use an IEC 320 C20 socket. Each chassis power
supply has a separate power cord. The power cord that you use to connect the blade server power supply units
to an AC power source will have an IEC 320 C19 plug on one end and on the other end one that conforms to
the AC power outlet specifications for your country. See the following table to determine which cord to order
for your blade server chassis power supply units. When you determine which power cord you need to order,
you can verify that its plugs conform to the power outlets for your facility by clicking on its reference link.
The jumper power cords, for use in racks, are available as an optional alternative to the standard power cords.
The optional jumper power cords have an IEC C19 connector (such as a Cisco RP Series PDU) on the end
that plugs into the chassis PDU and an IEC C20 connector on the end that plugs into an IEC C19 outlet
receptacle. For more information, contact your Cisco Systems representative.
Cisco UCS 5108 Server Chassis Installation Guide
91
Technical Specifications
Supported AC Power Cords and Plugs

Table of Contents

Other manuals for Cisco UCS 2208XP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco UCS 2208XP and is the answer not in the manual?

Cisco UCS 2208XP Specifications

General IconGeneral
BrandCisco
ModelUCS 2208XP
CategoryChassis
LanguageEnglish

Related product manuals